Leakage flow per square metre of a smoke barrier with a leakage area of 1.5 × 10⁻⁴ m² per m², calculated with the orifice equation and C = 0.65. Based on Klote (2002), p. 4-280, and Australian Building Codes Board (2020a), Data Sheet C5, pp. 149 to 150.
Original vector illustration for Fire curtain, level 2 Intermediate.
- Source basis: Klote (2002), p. 4-280 (Equation 5, C 0.6 to 0.7); Australian Building Codes Board (2020a), Data Sheet C5, p. 149 (Equation C5.1) and p. 150 (leakage area ratio, about 3 m³/h/m² at 200 °C and 25 Pa); Van Rossum (2027), §3.2 (density)
- Alt text: Line chart of leakage flow per square metre of barrier against pressure difference, for gas at 20 °C and at 200 °C.