Summary

Design area, sprinklers in the design area and minimum flow for a wet and a dry pipe system with the same density of 6.5 mm/min. Based on Hopkins et al. (2005), pp. 64 to 65 and McAllister et al. (2008), p. 76.

Original vector illustration for Dry pipe sprinkler system, level 2 Intermediate.

  • Source basis: Hopkins et al. (2005), p. 15 (30 % rule), pp. 64 to 65 (WTC 7 criteria); McAllister et al. (2008), p. 76 (loading dock spacing)
  • Alt text: Bar chart comparing wet and dry pipe design: area 139 and 181 m2, sprinklers 12 and 16, flow 910 and 1,190 L/min.