Heat release rate of a fast and a slow t-squared fire with the response of a heat detector and a sprinkler under a 4 m ceiling. Based on Schifiliti et al. (2002), pp. 4-10 and 4-21.
Original illustration for Detector activation time, level 4 Expert.
- Source basis: Schifiliti et al. (2002), p. 4-10 (power-law fire with fire growth time tg) and p. 4-21 (example 13: 4 m ceiling, sprinkler 74 °C and RTI 110, heat detector 57 °C and RTI 42, response times)
- Alt text: Two rising fire curves, fast and slow, with markers where a heat detector and a sprinkler respond; the fast fire is much larger at response.