Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-detector-activation-time-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 14 KB)

Summary

Temperature of the sensing element of two heat detectors in a steady ceiling jet of 153 °C and 2.4 m/s; the 57 °C rating is reached after about 11.6 s (RTI 55) and 6.3 s (RTI 30). Based on Schifiliti et al. (2002), p. 4-8.

Original illustration for Detector activation time, level 4 Expert.

  • Source basis: Schifiliti et al. (2002), p. 4-8 (example 1 and 2: kerosene pool fire, gas 153 °C and 2.4 m/s, RTI 55, rating 57 °C, response about 12 s); Ministry of Business, Innovation and Employment (2025b), p. 27 (heat detector RTI 30 and 57 °C)
  • Alt text: Line chart: element temperatures for RTI 55 and RTI 30 rise towards a 153 °C gas temperature and cross the 57 °C rating after 11.6 s and 6.3 s.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:28, 2 November 2026Thumbnail for version as of 17:28, 2 November 2026900 × 600 (14 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata