Contents
Fse-deflagration-to-detonation-transition-v4.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)
Summary
Pressure along a tube during a detonation of stoichiometric propane-air, using the approximations in the text: peak about twice the closed-vessel deflagration pressure, a plateau of 0.35 times the peak, and 2.76 times the peak after reflection from a rigid end. Based on Zalosh (2002), pp. 3-407 and 3-411.
Original illustration for Deflagration-to-detonation transition, level 4 Expert.
- Source basis: Zalosh (2002), p. 3-411 (PCJ = 2 Pm; plateau 0.35 PCJ; reflection 2.76 PCJ; Figure 3-16.7, redraw, do not copy) and p. 3-407 (Pmax of propane)
- Alt text: Pressure profile along a tube with a sharp peak at the detonation front, a lower plateau behind it and a higher reflected peak at a closed end.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:46, 2 November 2026 | 900 × 600 (9 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |