Contents
Fse-deflagration-to-detonation-transition-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 12 KB)
Summary
Critical pipe diameters derived from the detonation cell width: below one third of the cell width a detonation cannot propagate along a pipe, and below 13 cell widths it cannot pass from a pipe into a larger volume. The line marks a 1 cm fuel line. Based on Zalosh (2002), p. 3-412.
Original illustration for Deflagration-to-detonation transition, level 4 Expert.
- Source basis: Zalosh (2002), p. 3-412 (Table 3-16.4 and the Sc/3 and 13 Sc criteria) and p. 3-413 (Example 6, 1 cm fuel line)
- Alt text: Chart of two critical pipe diameters for nine gases on a logarithmic axis, with a vertical line at 1 cm.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:46, 2 November 2026 | 900 × 600 (12 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |