Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-common-cause-failure-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 10 KB)

Summary

Left: one detection system controls four functions, so its failure removes all of them. Right: revised design with early automatic suppression and smoke doors on local detectors. Based on Australian Building Codes Board (2020b), p. 100.

Original illustration for Common cause failure, level 4 Expert.

  • Source basis: Australian Building Codes Board (2020b), p. 100 (example: detection system raises alarm, activates smoke control, alerts fire brigade, releases hold-open smoke doors; total failure probability about 20 %; redesign with early automatic suppression in lieu of active smoke control and smoke doors on local detectors independent of the main system, detection system retained)
  • Alt text: Two panels: left, one detection system feeds alarm, brigade call, smoke control and smoke doors; right, sprinklers and local door detectors added.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:38, 2 November 2026Thumbnail for version as of 17:38, 2 November 2026900 × 600 (10 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata