Summary

Maximum ceiling jet temperature rise under a 5 m ceiling for steady fires of 0.5, 1 and 2.5 MW, with a 10 °C smoke detector criterion and the 37 °C rise for a 57 °C heat detector in a 20 °C room. Based on National Research Council of Canada et al. (2005), p. 2.7-3, and Iqbal and Salley (2004), p. 11-7.

Original vector illustration for Ceiling jet, level 2 Intermediate.

  • Source basis: National Research Council of Canada et al. (2005), p. 2.7-3 (correlation and constants); Alpert (2002), p. 2-19 (validity: steady fires, unconfined ceilings); Iqbal and Salley (2004), p. 11-7; Ministry of Business, Innovation and Employment (2025b), p. 27
  • Alt text: Line chart: ceiling jet temperature rise under a 5 m ceiling falls with distance for fires of 0.5, 1 and 2.5 MW, crossing detector thresholds.