Summary
C/VM2 design fire for car parks without stacking (0.0117 t²) compared with the fast fire (0.0469 t²), with measured peaks of single cars. Based on Ministry of Business, Innovation and Employment (2025b), p. 20, and Babrauskas (2002b), p. 3-27.
Original vector illustration for Car park fire, level 2 Intermediate.
- Source basis: Ministry of Business, Innovation and Employment (2025b), p. 20 (Table 2.3.2.1); Babrauskas (2002b), p. 3-27; Van der Graaf et al. (2021/2023), p. 25
- Alt text: Two t-squared curves: car park growth reaches 6 MW after 12 minutes, the fast curve after 6 minutes; dashed lines mark car peaks.