Mass flow at the design level 3 m above the balcony (6 m above the fire) for the worked example, by method. Based on Cooper (2002b), pp. 3-232 to 3-233, and Milke (2002b), p. 4-301.

Original illustration for Balcony spill plume, level 4 Expert.

  • Source basis: Cooper (2002b), p. 3-232 (example: 26.0 and 34.2 kg/s, 31 % increase) and p. 3-233 (alternative solution, 68 kg/s, about 2.0 and 2.6 times); Milke (2002b), p. 4-301 (Eq. 29) and p. 4-302 (Eq. 32)
  • Alt text: Bar chart of plume mass flow 6 m above a 5 MW fire: in the open 26.0, line plume 34.2, Milke's equation 62.9 and Cooper's alternative 68 kg/s.