Skip to content
From Fire Safety Academy Wiki
Contents
  1. 1Summary
  2. 2Licensing

Fse-adiabatic-surface-temperature-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 12 KB)

Summary

Net heat flux into the painted floor object of the worked example (convective coefficient assumed at 25 W/(m²·K)) against its surface temperature; the flux becomes zero at the adiabatic surface temperature of about 377 °C. Based on McGrattan et al. (2026), pp. 77–79, and Van Rossum (2027), §4.7.

Original illustration for Adiabatic surface temperature, level 4 Expert.

  • Source basis: McGrattan et al. (2026), pp. 77–79 (heat balance); Van Rossum (2027), §4.7 (20 kW/m²), §5.2 (hc 20–25 W/(m²·K) for a fully developed fire, 25 for a standard fire; assumed), §5.4 (σ, emissivity)
  • Alt text: Line chart: net heat flux into the floor object falls from 17.6 kW/m² at 20 °C to zero at 377 °C, the adiabatic surface temperature.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:25, 2 November 2026Thumbnail for version as of 17:25, 2 November 2026900 × 600 (12 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata