Static electricity is electric charge that is trapped on or in a nonconductive body, or held on a conductor that is isolated from the earth, so that it cannot flow away.[1] It forms when contacting surfaces, usually of dissimilar materials and at least one a poor conductor, are pulled apart.[2] A charge in itself might not be a fire or explosion hazard; there must also be a discharge, a sudden recombination of the separated charges.[1] Such a discharge is an ignition source for flammable gases, vapours, mists and dusts when its energy exceeds the minimum ignition energy of the mixture.[3] Optimum mixtures of saturated hydrocarbon vapours in air need only about 0.25 mJ, which a discharge from a fingertip can deliver.[3]

Static electricity is therefore a concern in liquid transfer, powder handling, dust explosion prevention and electrostatic spray finishing.[4][5] Control rests on removing the ignitable mixture, letting charge leak away through humidity, bonding and grounding or ionised air, and, where that is not possible, inerting or ventilation.[4] This article follows mainly the Fire Protection Handbook (2008), which describes US practice and refers to NFPA 77, Recommended Practice on Static Electricity.[1]

Definition and basic concepts

The Fire Protection Handbook uses the term for the electrification of materials and for the effects of the positive and negative charges so formed, particularly where their release is a fire or explosion hazard.[1] Neither the SFPE Handbook nor Introduction to Fire Safety Engineering gives a separate definition. Electricity moves freely through conductors such as metals.[1] It flows with difficulty or not at all through nonconductors, also called insulators or dielectrics, which include gases, glass, resin, most synthetic plastics and most petroleum oils.[1] A charged body always has an equal and opposite charge somewhere else, because electrons removed from one body must go to another.[3][6]

Charge is measured in coulombs, potential in volts and current in amperes; static currents are usually in the microampere range.[6][4] Two conductive bodies separated by an insulator form a capacitor, and in many static problems one of the bodies is the earth and the insulator is air.[3] Capacitance is the ability to store charge; a larger body needs more electrons to reach a given voltage and so has a higher capacitance.[6] Static charges show up only where highly insulated bodies or surfaces are present.[3] Problems arise where charge accumulates faster than it dissipates.[3]

How charge is separated

When two dissimilar materials touch, electrons tend to pass from one to the other.[2] Separating them takes work, and that energy reappears as a voltage between the two surfaces.[2] If a conductive path exists the charges reunite at once; if not, as with insulators, they remain and an electric field forms.[2] Charge formed this way is called frictional or triboelectric charging.[2]

Common industrial examples are friction between surfaces, wet steam or particle-laden gas escaping from a pipe, and a liquid stream leaving a hose or spout.[2] Others are powders passing through chutes or pneumatic conveyors, moving nonconductive belts and moving vehicles.[2] A conductor brought into the field of a charged object develops separate regions of opposite charge by induction.[2] An object can also pick up charge by contact, as a pail does from a charged falling stream.[2] Corona ions and charge injection by electron beams or high-voltage electrodes are further mechanisms, usually intentional.[2] Because the origins of static electricity exist at every interface, separation cannot be prevented absolutely; most measures therefore aim to let charges recombine harmlessly before sparking potentials are reached.[2]

Charge on a nonconductor stays where it was formed, and a spark drawn from such a surface discharges only a small area and seldom ignites anything.[2] On a conductor the charge is free to move, so an isolated conductor can release all its stored energy in one incendive spark.[2] Charges induced on insulated conductors are therefore often more dangerous than the originally separated charges.[3] On sharp points the field can exceed the breakdown strength of air, about 3,000,000 V/m (3 kV/mm), producing corona or brush discharge.[2]

Stored energy and discharge types

The energy released when a charged conductor discharges follows from its capacitance and voltage.[3] Doubling the voltage gives four times the energy:[3]

E=12CV2=12QV=Q22C

Symbol Description Unit
E Stored energy J
C Capacitance of the conductive body F
V Voltage of the body relative to its surroundings V
Q Charge (Q = CV) C

Only part of the stored energy reaches the mixture, because some heats the electrodes.[3] The spark breakdown voltage has a minimum of about 350 V at a gap of about 0.01 mm, and wider gaps need proportionately higher voltages.[3] At very close spacing the electrodes can absorb enough heat to prevent ignition.[3]

Worked example. Zalosh (2002) considers an elevated silo with a capacitance of 500 pF that stores a pharmaceutical powder.[7] The powder has a minimum ignition energy of 10 mJ for inductive sparks and 50 mJ for capacitive sparks.[7] Rearranging the energy equation gives V = √(2E/C) = √(2 × 0.050 / (500 × 10−12)) ≈ 14,000 V, or 14 kV.[7] Zalosh notes that such voltages can indeed arise from impact and friction of the powder during filling and unloading.[7] Grounding the silo prevents this, but ungrounded objects inside and a highly resistive powder can still hold charge.[8] For an optimum saturated hydrocarbon vapour mixture, which needs about 0.25 mJ,[3] the same 500 pF conductor would need only about 1,000 V.

Rising curve of voltage against stored energy for a 500 picofarad conductor with markers for hydrogen, methane, propane, acetone and a powder
Voltage at which a 500 pF conductor stores a given spark energy, with minimum ignition energies of selected fuels.

Discharges through air range, in increasing intensity, from corona through brush and spark to propagating brush discharge.[3] Corona is a faint blue glow, often with a hissing sound, that usually cannot ignite ordinary gases and vapours, although acetylene, carbon disulfide and hydrogen are exceptions.[6] Brush discharges can ignite gases and vapours but not common dusts.[3] Sparks and propagating brush discharges can ignite gases, vapours and dusts.[3] A propagating brush discharge comes from a thin insulator, less than 6 mm thick, backed by a conductive surface; it spreads over several square centimetres with a loud pop.[4]

Four panels showing corona, brush, spark and propagating brush discharges with ticks for gases, vapours and dusts
Types of electrostatic discharge in order of increasing intensity and the mixtures they can ignite.

Ignition energies

Static electricity causes ignition only if four conditions are met together.[1] There must be an effective means of separating charge and a means of accumulating it at a sufficient potential difference.[1] There must be a discharge of adequate energy, and that discharge must occur in an ignitable mixture.[2] Iqbal and Salley (2004) give the same four conditions, naming a spark gap as the third, and note that removing any one of them eliminates the static ignition hazard.[9]

Chain of four linked boxes: charge separation, accumulation, discharge of adequate energy, ignitable mixture, with control measures under each link
The four conditions for ignition by static electricity and the control measures that break each link.
Minimum ignition energy of selected gases and vapours in dry air at 1 atm and 25 °C
Fuel MIE (mJ)
Hydrogen 0.016
Acetylene 0.017
Methane 0.21
Propane 0.24
Acetone 1.15
Ammonia 680

Values from Table 17.8.3 of Ural and Garzia (2008), adapted from Britton (1999).[10] Scarbrough (2008a) gives 0.017 mJ for both hydrogen–air and acetylene–air mixtures.[11] L. J. Moore (2008) notes that 0.3 mJ can ignite methane, about one-fiftieth of the static charge a person accumulates walking across a carpet on a dry day.[12]

Dust clouds generally need more energy than gases.[11] A minimum dust concentration exists below which no spark can ignite the cloud, and near that concentration a relatively high energy is needed.[11] Layers of metallic dusts such as aluminium, magnesium, titanium and zirconium need less energy than carbonaceous materials.[11] Zalosh (2002) adds that a short capacitive electrostatic discharge needs more energy to ignite a dust cloud than the longer spark from an electromechanical switch.[7] Because dust clouds need high ignition energies, Schwab (2008c) advises that blaming a dust explosion on static electricity should be held suspect without definite evidence.[13] Electrostatic discharges have nevertheless initiated explosions of dusts with high resistivity and low ignition energy, such as tantalum.[14]

Control measures

Removing ignitable mixtures from places where static sparks can occur is the surest way to prevent static-caused fires.[3] Where that is not possible, an existing charge can be drained by lowering the resistance to ground or neutralised by adding charge of opposite polarity.[3] If the resistance to ground is below 1 MΩ, no practical system accumulates charge fast enough to ignite ordinary gases, vapours or dusts.[3] Resistances up to 1,000 MΩ may be adequate in many cases, but fast charge generation, as in pneumatic transport, may need 1 MΩ.[3] Such resistances should be measured at 500 V or more so that films of paint or grease break down.[3]

Worked example. Resistance is the ratio of voltage to current, so a body charged by a constant current settles at a voltage V = IR.[4] With a charging current of 1 µA, typical of the microampere range of static currents, a 1 MΩ path to ground holds the body at about 1 V.[15] A 1,000 MΩ path holds it at about 1,000 V, at which a 500 pF object stores ½ × 500 × 10−12 × 1,0002 = 0.25 mJ. That equals the ignition energy of hydrocarbon vapours, which shows why faster charging calls for a lower resistance.[3]

Humidity makes many materials, such as paper, wood, fabrics and concrete, conductive enough to drain charge.[15] A relative humidity of about 50 % or more at normal room temperature is usually stated to avoid static problems with such materials.[15] It does not help with heated surfaces, with charges inside oils or other insulating liquids and solids, and water vapour does not make the air itself appreciably conductive.[15] Ouellette (2008) adds that plastics, with low water absorption and high resistivity, cannot be discharged this way.[16]

Where natural paths are lacking, artificial conducting paths are made by bonding conductive objects to each other and grounding them to earth.[15] Ionisation offers a third route.[17] A grounded static comb, a metal bar with needle points, ionises the air near a charged surface so that the charge leaks away.[17] Line-powered electrical neutralisers do the same but should not be used where flammable vapours, gases or dusts may be present unless specifically approved.[17] Radioactive sources and open flames can also ionise the air.[17] Where charges cannot be dissipated, inert gas or interlocked mechanical ventilation can keep the mixture outside its flammable range.[17]

Liquids, gases and dusts

Liquids of low conductivity become charged when they flow through pipes or are mixed, poured, pumped, filtered or agitated.[17] With high flow velocity or filtration through nonconducting media, a spark can occur even when all conductive equipment is grounded.[17] If the conductivity of a hydrocarbon liquid exceeds 50 pS/m, charges dissipate harmlessly provided the equipment is grounded.[18] Charge that reaches the surface of the liquid in a grounded tank decays over a relaxation time of a fraction of a second to several minutes.[18] No bonding or grounding of the tank can remove this internal surface charge; inerting, enrichment above the upper flammable limit or conductivity additives are used instead.[18][11] Ordile (2008) lists excessive turbulence, pumping two dissimilar materials, free fall through the vapour space and very fine filters as likely causes of static fires in tanks and tank vehicles.[19]

A metal can on an insulating surface behaves differently: a free charge appears on its outside and can spark to a grounded fill pipe.[18] Scarbrough (2008a) names a gasoline can filled on the plastic bedliner of a pickup truck as an example, controlled by placing the can on the ground.[18] During container filling, the nozzle should touch the container before flow starts and stay in contact until filling ends.[17] Mists and foams can be ignited by static sparks much as dusts can, even below the flashpoint of the liquid.[11] Iqbal and Salley (2004) cite Howells (1993) on fires in floating-roof tanks that appear to have been ignited by static electricity from foam injection.[20]

Three filling arrangements: nozzle touching a can, a can on an insulating support with a bond wire, and a can on a conducting support
Bonding of flammable liquid containers during filling.

Clean gases do not become charged when they flow, but gases carrying dust, metallic oxides, scale or liquid droplets can become charged.[11] High-pressure carbon dioxide should not be discharged into flammable atmospheres because the snow it forms can produce static sparks.[11] Pure hydrogen generates no charge, but hydrogen carrying oxide particles from pipes and containers can.[11] In a US nuclear plant event reviewed by Nowlen et al. (2005b), static electricity from escaping hydrogen was suspected of igniting a leak from a storage cylinder.[21]

Charge generation in moving dust normally cannot be prevented.[11] In most proven cases of static ignition of dust, the spark jumped between an insulated conductor and ground.[11] Propagating brush discharges have ignited dust inside pneumatic transport systems with thin-walled insulating hose.[11] Self-discharge within a dust cloud, like lightning, has not been verified experimentally in silos of up to 5 m (16 ft) radius.[11][6]

Industrial applications and regulation

In the United States, the 2008 handbook points to NFPA 77 for detailed guidance on bonding and grounding, together with process standards such as NFPA 30 and NFPA 33.[4][5] Spray finishing is done in a spray booth, room or area, and Scarbrough (2008b) calls static electricity a common source of flammable vapour ignition in electrostatic spray finishing.[5] Energised electrodes send charge into the air, which collects on nearby surfaces and can raise them to a high voltage.[5] Electrostatic spray systems should have interlocks that de-energise the power supply when the guns are not spraying, and most modern listed guns limit discharge energy below the ignition level.[5] All parts of the fluid and spray system, the workpiece and every conductive object within 3 m (10 ft) of charged elements should be bonded together and grounded.[5]

The operator is a conductor too and is grounded by holding the grounded gun with a bare hand or by wearing conductive-soled shoes on a grounded floor.[5] Walking on sticky paint residue can charge a person in the same way as walking on a wool or nylon carpet, and the resulting spark can ignite flammable vapours.[5] In powder coating, the powder is charged from a direct-current supply of 60 to 120 kV and attracted to the grounded workpiece.[22] In plastics plants, film stripping, films passing over rolls and power belts generate static, and Ouellette (2008) names induction (tinsel), grounding and ionisation as the three neutralising methods.[16]

In grain handling, research found that electrostatic sparks were generally not a problem except where high charge generation met poor grounding.[23] Nonconductive belting in bucket elevators can still charge the buckets, so conductive belting and good grounding are prudent.[24] US OSHA rules described by Maness and Sargent (2008) call for a belt surface resistivity below 100 MΩ.[24] Typical values are about 1 MΩ for rubber belting and 15 MΩ for PVC belting.[24]

Detection and limitations

Several instruments detect static charge.[6] A leaf electroscope shows its presence, and a small neon lamp glows feebly when touched to a conductor at 70 V or more.[6] Field mills give a continuous reading of the field from a distant charge, electrostatic voltmeters cover ranges from 100 to 10,000 V, and electrometers serve laboratory and field investigations.[6]

Several common beliefs are only partly true. Humidification is not a cure for all static problems, and grounding a tank does not remove the charge on the surface of the liquid inside it.[15][18] Spark energies from nonconductors are usually too small for ignition, yet propagating brush discharges from thin insulators are an exception.[2][11] For dust clouds, the minimum ignition energy also depends on the type of spark, since short capacitive electrostatic discharges need more energy than long inductive sparks.[7] Finally, the handbook describes US practice around 2007 and refers to the NFPA catalogue for current editions of the standards it names.[4]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Scarbrough (2008a), p. 11-59.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 Scarbrough (2008a), p. 11-60.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 3.21 Scarbrough (2008a), p. 11-61.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 Scarbrough (2008a), p. 11-67.
  5. ↑ 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 Scarbrough (2008b), p. 9-34.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.7 Scarbrough (2008a), p. 11-66.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 Zalosh (2002), p. 3-405.
  8. ↑ Zalosh (2002), pp. 3-405–3-406.
  9. ↑ Iqbal and Salley (2004), p. F-62.
  10. ↑ Ural and Garzia (2008), p. 17-147.
  11. ↑ 11.00 11.01 11.02 11.03 11.04 11.05 11.06 11.07 11.08 11.09 11.10 11.11 11.12 11.13 Scarbrough (2008a), p. 11-65.
  12. ↑ L. J. Moore (2008), p. 9-214.
  13. ↑ Schwab (2008c), p. 6-142.
  14. ↑ Zalosh (2008), p. 2-100.
  15. ↑ 15.0 15.1 15.2 15.3 15.4 15.5 Scarbrough (2008a), p. 11-62.
  16. ↑ 16.0 16.1 Ouellette (2008), p. 9-62.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 17.6 17.7 Scarbrough (2008a), p. 11-63.
  18. ↑ 18.0 18.1 18.2 18.3 18.4 18.5 Scarbrough (2008a), p. 11-64.
  19. ↑ Ordile (2008), p. 7-29.
  20. ↑ Iqbal and Salley (2004), p. B-60.
  21. ↑ Nowlen et al. (2005b), p. N-4.
  22. ↑ Scarbrough (2008b), p. 9-28.
  23. ↑ Maness and Sargent (2008), p. 9-95.
  24. ↑ 24.0 24.1 24.2 Maness and Sargent (2008), p. 9-98.

References

  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Maness, J. E., & Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-85–9-103). National Fire Protection Association.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • Nowlen, S. P., Najafi, B., Wyant, F. J., Forester, J., Kazarians, M., Kolaczkowski, A., Joglar, F., Funk, D., Hannaman, G., & Anoba, R. (2005b). EPRI/NRC-RES fire PRA methodology for nuclear power facilities: Vol. 2. Detailed methodology (NUREG/CR-6850; EPRI 1011989). Electric Power Research Institute; U.S. Nuclear Regulatory Commission, Office of Nuclear Regulatory Research.
  • Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
  • Ouellette, G. (2008). Plastics industry and related process hazards. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-53–9-65). National Fire Protection Association.
  • Scarbrough, D. R. (2008a). Control of electrostatic ignition sources. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-59–11-68). National Fire Protection Association.
  • Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
  • Schwab, R. F. (2008c). Dusts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-141–6-152). National Fire Protection Association.
  • Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
  • Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.