An ESFR sprinkler (early suppression fast-response sprinkler) is an automatic sprinkler head designed to suppress a rapidly growing fire in stored goods. Heat opens the sprinkler, and its spray carries water down through the rising hot gases to the burning material. Suppression means a sharp, sustained fall in the rate at which the fire releases heat. Water has to reach the fuel while the fire is still small enough for that outcome.[1][2]
In a warehouse fire, water from the ceiling may have to pass through a rising plume and penetrate several tiers of stored goods. A tested arrangement can provide suppression from ceiling level alone. Its suitability depends on the goods, the way they are stacked, the building geometry and the available water supply. A change from open racks to solid shelving can alter the route by which water reaches the fire.[3]
How heat and water reach the fire
Hot gases rise in the fire plume and spread beneath the ceiling. When those gases heat an individual sprinkler's operating element to its release temperature, the sprinkler opens. Its response time index describes how readily the element heats up in a moving stream of hot gas. The actual opening time also depends on the temperature and speed of the gas reaching the sprinkler.[4][5]
Once the sprinkler opens, the rising gas and descending droplets move in opposite directions. Droplets with enough momentum can reach the burning surfaces. If sufficient water gets there, it cools the fuel and reduces the rate of burning. A sprinkler intended for fire control can limit spread by wetting adjacent stock, even while material within the original fire area continues to burn.[6]
What storage fire tests measure
Researchers distinguish the water the fire needs from the water the sprinkler delivers. In a required delivered density test, pipes distribute water just above the fuel. The researchers vary the application rate and measure the fire's heat release to identify the rate that gives sustained suppression. In an actual delivered density test, collection pans above a burner measure how much of a sprinkler's discharge passes through a rising plume. Different pans can collect different amounts under the same sprinkler.[1]
One series used a standard plastics commodity in racks. For three, four and five tiers of storage, the recorded required delivered densities were 14.4, 18.5 and 26.7 mm/min, respectively. Applying those research values to a different commodity would assume it responds to water in the same way. Tests with upholstered furniture and cartoned plastics showed that fuel packages with similar fire growth could need different water application rates.[7]
Flow through one sprinkler
For an open sprinkler discharging water, the flow rises with the square root of the pressure at the sprinkler. The K-factor is the experimentally determined discharge coefficient for the particular sprinkler model.[8]
| Symbol | Quantity | Unit |
|---|---|---|
| Q | Flow from one open sprinkler | L/min |
| K | Metric discharge coefficient | L/min per √bar |
| p | Gauge pressure at that sprinkler while water flows | bar |
For example, the 2008 Fire Protection Handbook gives 3.4 bar for one historical arrangement of Class IV goods, a US commodity category. The entry covers open racks without solid shelves or open-top containers, a maximum storage height of 6.1 m and a maximum ceiling height of 9.1 m. Using the illustrated nominal metric coefficient of 200 gives a flow of about 369 L/min from one sprinkler. That calculation gives the water leaving the orifice. The amount reaching the fuel still depends on the plume and the spray distribution.[9][1]
Matching protection to the warehouse
The assessment starts with the complete unit of storage. In commodity classification, the pallet, packaging and contents can all change how a load burns. Sprinkler hazard classification identifies the hazard to be protected. A sprinkler design density describes a water application rate per unit of area. For an ESFR sprinkler, full-scale tests establish which rack arrangements the spray can protect.[3][5]
The designer checks rack and ceiling heights, shelves, ceiling obstructions and whether the arrangement calls for in-rack sprinklers. The hydraulic calculation then establishes whether the water supply can support the required operating sprinklers together. Building services also matter. Australia's Fire Safety Verification Method data sheets describe how early operation of smoke exhaust can remove hot gases before they heat the sprinklers. This interaction is relevant when the design relies on early suppression.[2][3][8][10]
See also
- Sprinkler skipping
- Quick-response sprinkler
- Control mode specific application sprinkler
- Storage height and clearance
Notes
- ↑ 1.0 1.1 1.2 Fleming (2008), chap. 16.1, pp. 16-10–16-11.
- ↑ 2.0 2.1 Isman (2008), chap. 16.2, p. 16-27.
- ↑ 3.0 3.1 3.2 Golinveaux (2008), chap. 16.5, pp. 16-72–16-73, 16-79 and 16-83–16-85.
- ↑ Fleming (2008), chap. 16.1, pp. 16-3–16-5.
- ↑ 5.0 5.1 Fleming (2002), chap. 4.3, pp. 4-72–4-73.
- ↑ Fleming (2008), chap. 16.1, pp. 16-7–16-11.
- ↑ Fleming (2008), chap. 16.1, p. 16-11, table 16.1.2 and fig. 16.1.14.
- ↑ 8.0 8.1 Fleming (2002), chap. 4.3, p. 4-75.
- ↑ Golinveaux (2008), chap. 16.5, p. 16-83, table 16.5.7. Isman (2008), chap. 16.2, p. 16-27, fig. 16.2.26. Calculation using Fleming (2002), p. 4-75.
- ↑ Australian Building Codes Board (2020), §1.5.4.3, p. 21.
References
- Australian Building Codes Board. (2020). Fire safety verification method: Data sheets (Version 1.1).
- Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed., chap. 4.3). National Fire Protection Association and Society of Fire Protection Engineers.
- Fleming, R. P. (2008). Principles of automatic sprinkler system performance. In A. E. Cote (Ed.), Fire protection handbook (20th ed., chap. 16.1). National Fire Protection Association.
- Golinveaux, J. E. (2008). Sprinkler systems for storage facilities. In A. E. Cote (Ed.), Fire protection handbook (20th ed., chap. 16.5). National Fire Protection Association.
- Isman, K. E. (2008). Automatic sprinklers. In A. E. Cote (Ed.), Fire protection handbook (20th ed., chap. 16.2). National Fire Protection Association.