Aircraft rescue and firefighting (ARFF) is the specialised fire service that protects the occupants of an aircraft involved in an accident or incident at or near an airport. Its main task is to keep an escape area around the fuselage free of fire long enough for the occupants to get out, and to rescue those who cannot.[1][2] ARFF crews use purpose-built vehicles that carry their own water, foam concentrate and complementary agents, because a fuel fire can make an intact cabin unsurvivable within about three minutes.[3]

In the handbook's 2008 account, airport protection levels depend on aircraft size and, under US rules, operation frequency. The US rules were in 14 CFR Part 139, the international rules in ICAO Annex 14; NFPA 403 set stricter response times.[4][5][6] Agent quantities rest on a critical fire area next to the fuselage, a foam application rate and a control time of one minute.[7] This article describes the rules as reported in the 2008 handbook.

Mission and organisation

The handbook gives rescue a specific meaning: the control of life-threatening fire in the critical area during the time needed for all physically able occupants to evacuate themselves.[2] Fire control then continues so that occupants who are badly injured or trapped can be freed. Assisted rescue from small aircraft is often routine, but in aircraft with many occupants it is usually not possible in the time available.

Airport fire services are organised in several ways. In the United States some airport fire fighters belong to the municipal or state fire department, while others work for the airport or port authority. A few airports use private contractors.[1] Small airports may rely on maintenance, security or operations staff who are cross-trained for ARFF duties.[8] Some departments cover all hazards, from structural fires to water rescue, while others handle only ARFF.[9] The operational priorities are those of all firefighting: rescue, fire control, loss control and environmental protection, in that order.[10]

Escape time and survival time

Fuel is the one element present in every powered aircraft, so the fire service plans for a survivable crash followed by a fuel fire.[9] After an impact, fuel can escape from damaged tanks as a mist that ignites easily on broken wiring or hot engine parts. The fireball then ignites other combustibles, including pools of high-flashpoint Jet A fuel.[11] A liquid fuel burns only once it has turned into vapour or mist, and in a pool fire this happens by evaporation from the surface.[12] Turbine engines can remain an ignition source for many minutes after a nominal shutdown.[11]

In a 1965 study for the US Federal Aviation Administration (FAA), Conley defined escape time as the time from the start of the fire until a tolerance limit for heat or carbon monoxide prevents escape.[13] In a C-97 fire test reported in that study, the cabin stayed at 21 °C (70 °F) for 2 minutes while a spill fire burned outside. Burn-through occurred at 130 seconds, and at 138 seconds the cabin had reached unsurvivable temperatures.[13]

Cabin materials have since been improved to increase survival time, yet the margin is still small.[4] In a fuel spill fire the aluminium skin burns through in about one minute, but the insulation of an intact fuselage keeps the cabin survivable until the windows melt out after about three minutes.[3] The handbook likewise gives survival in an exposed intact large aircraft as little as 3 minutes.[14] In an FAA study the air at the cabin ceiling reached 704 °C (1300 °F) within 50 seconds with the doors open. With all but one door closed it still reached 204 °C (400 °F) in the same time.[15]

Timeline from 0 to 300 seconds comparing fuselage burn-through and cabin survival with ARFF response and one-minute control time
Time scale of a post-crash fuel fire compared with ARFF response and control requirements.

Most deaths in survivable accidents happen after the impact. A study of US National Transportation Safety Board (NTSB) reports on 60 survivable accidents found that 78 % of the fatalities occurred after impact, and that 95.4 % of these were caused by smoke inhalation or burns.[15] In large turbine aircraft the post-accident fire is the more important cause of death, whereas in light aircraft more people die of impact trauma.[16] Fire inside the fuselage is treated in Aircraft cabin fire.

Regulations and airport categories

In the United States the FAA received the authority to issue airport operating certificates in 1970, and the requirements are in Title 14 of the Code of Federal Regulations, Part 139 (14 CFR Part 139).[4] Part 139 sets requirements for personnel, agent quantities and response times. ICAO, a United Nations agency founded in Chicago in 1944, sets international standards and recommended practices. NFPA publishes its own ARFF standards, and the three sets do not fully agree, which makes it difficult to standardise equipment and training.[4]

The main NFPA documents are NFPA 403 for ARFF services, NFPA 402 for operations and NFPA 414 for vehicles.[15] NFPA 1003 and NFPA 405 cover the qualification and recurring proficiency of airport fire fighters. Each system places an airport in an index or category based on aircraft size.

In the cited 2004 Part 139, the FAA index (A to E) depends on aircraft length and departures. The longest group with at least five average daily departures sets the index. If the longest group has fewer than five, the next lower index applies, with A as the minimum.[5][15] ICAO and NFPA use ten categories based on aircraft length and width, from category 1 (Cessna 182) to category 10 (Antonov AN-225, Airbus A380).[5]

Under that version of Part 139, during operations with only aircraft shorter than the airport's normal index group, ARFF capability could be reduced to the index of the longest aircraft then operating. The handbook calls this remission; NFPA 403 had no such provision.[7] The handbook chapters disagree on ICAO: one says it ended remission in January 2005, the other that it still allowed it.[7][17] Part 139 gave no staff minimum, requiring enough personnel to operate vehicles, meet response times and achieve discharge rates.[5] FAA Advisory Circular 150/5210-6B recommended levels of protection well above the Part 139 minimum.[18] The table compares the agent and vehicle criteria reported by the 2008 handbook for six categories.

Minimum water for foam production and minimum number of ARFF vehicles per airport category (US figures converted to m³)[19][20]
Category (FAA index) Example aircraft ICAO water Q1 + Q2 (m³) FAA water Q1 + Q2 (m³) NFPA water Q1 + Q2 + Q3 (m³) Vehicles ICAO / FAA / NFPA
4 (A) DHC-8-100 2.40 0.38 5.07 1 / 1 / 1
6 (B) B737-300; Emb-145 7.90 5.68 14.2 2 / 1–2 / 2
7 (C) B757 12.1 11.4 18.5 2 / 2–3 / 3
8 (D) A300; B767-300 18.2 15.1 29.5 3 / 3 / 3
9 (E) B747-200; A340-400 24.3 22.7 36.2 3 / 3 / 4
10 (n/a) AN-225; A380 32.3 n/a 54.0 3 / n/a / 4

Extinguishing agents and quantities

The agent quantities rest on the critical area concept, used by ICAO and NFPA since the early 1970s and still the standard more than three decades later.[7] NFPA 403 defines the theoretical critical area (TCA) as "the fire area adjacent to the aircraft that must be controlled to ensure temporary fuselage integrity and to provide an occupant escape area". It is a rectangle calculated from the length and width of the aircraft, meant to categorise aircraft rather than to represent a real fuel spill. The practical critical area (PCA) is two-thirds of the TCA, a ratio based on data from actual aircraft fires and adopted by the ICAO Rescue and Fire Fighting Panel.[7][3] The formula assumes a standard fuselage height, which full-length double-deck aircraft such as the A380 have made unreasonable.[7]

The panel defined control time as the time from the arrival of the first vehicle until the fire intensity is reduced by 90 %.[7] FAA, NFPA and ICAO all use a control time of one minute.[3] In 1972 the panel found an application rate of 0.13 US gallons per minute per square foot (gpm/ft²), about 5.3 L/min/m², suitable for aqueous film-forming foam (AFFF), and 0.15 gpm/ft² (6.1 L/min/m²) for protein foam.[7] Scheffey gives the ICAO rates as 5.5 L/min/m² for AFFF and 8.2 L/min/m² (0.20 gpm/ft²) for protein foam, so the two sources differ on protein foam.[21] These rates go back to large JP-4 pool fire tests, some with a real fuselage.[22]

The required water has three parts. Q1 is the water needed to control a fire in the PCA within one minute, equal to the area times the foam application rate times the application time.[19] Q2 keeps the fire under control after the first minute, and it is a factor f times Q1, with f ranging from 3 % for category 1 to 170 % for category 8. Q3 is water for interior firefighting, from none at categories 1 and 2 to about 1900 L/min (500 gpm) for 10 minutes at category 10. Only NFPA includes Q3 in its totals.

Plan view of an aircraft inside a theoretical critical area rectangle with a smaller practical critical area, beside a stacked bar of Q1, Q2 and Q3
Critical fire areas around a fuselage and the three parts of the water quantity used by NFPA 403.

Q1=APCARTQ2=fQ1Q=Q1+Q2+Q3

Q˙=m˙″ΔHc,effAf(1−e−kβD)

Symbol Description Unit
Q1,Q2,Q3 Water for one-minute control, for continued control, and for interior firefighting L
APCA Practical critical area, two-thirds of the theoretical critical area m²
R Application rate of foam solution for the foam type L/(min·m²)
T Application time, 1 min for control min
f Factor per airport category (0.03 to 1.7 for categories 1 to 8) –
Q˙ Heat release rate of the fuel fire kW
m˙″ Burning rate per unit area kg/(m²·s)
ΔHc,eff Effective heat of combustion kJ/kg
Af Horizontal burning area m²
kβ Empirical constant for the fuel m⁻¹
D Diameter of the burning area m

The second equation, used in NUREG-1805, estimates the heat release rate of the fuel fire from its burning rate, heat of combustion and area.[23] A worked example uses a test series in which AFFF was applied at 250, 400 and 800 gpm to JP-4 fires of 743 m² (8000 ft²).[21] The application rate is the flow divided by the fire area, so 3030 L/min (800 gpm) gives 4.1 L/min/m² (0.10 gpm/ft²). A flow of 946 L/min (250 gpm) gives only 1.3 L/min/m² (0.03 gpm/ft²), a rate at which the cited test recorded no fire control or extinguishment.[21] Control time rises exponentially as the rate falls, particularly below 4.1 L/min/m².[24]

Bar chart of AFFF application rate on a 743 square metre JP-4 fire for flows of 946, 1514 and 3028 litres per minute with design-rate line
Application rate of AFFF solution on a 743 m² JP-4 test fire for three flow rates, compared with the ICAO design rate.

Controlling the same area at 5.5 L/min/m² within one minute takes Q1 = 743 × 5.5 × 1 ≈ 4090 L (1080 gal). That is about a third of the 11,360 L (3000 gal) water tank of a large ARFF vehicle.[25] With the JP-4 values of 0.051 kg/(m²·s), 43,500 kJ/kg and kβ = 3.6 m⁻¹ and a diameter of 31 m, the bracket is practically 1.[26] The fire then releases about 1650 MW, some 660 times the 2.5 MW of a burning 1 m² gasoline pool.[27] In small JP-5 and JP-8 spill tests on concrete, unconfined fires burned at about one-fifth of the corresponding pool rate; for large releases, Gottuk and White recommend pool rates as the conservative choice.[28]

Every index airport must also carry at least 227 kg (500 lb) of dry chemical powder or of a clean halogenated agent such as Halon 1211 or Halotron.[25] The secondary agent is needed for three-dimensional fuel fires.[3] Foam cannot extinguish falling-fuel or pressure fires unless the fuel has a high flashpoint and can be cooled by the water in the foam.[29]

The 2008 handbook described AFFF as the standard foam at US airports and said the FAA required it to meet military specification MIL-F-24385 so that concentrates in bulk and vehicle tanks were compatible.[25] Its low viscosity and the film it forms on kerosene make it particularly suitable for jet fuel spill fires.[29] The handbook reported that other foam formulas were favoured in much of Europe.[16] Fluorinated surfactants in AFFF raise environmental concerns; in the account published in 2008, a major producer had agreed with the US Environmental Protection Agency to stop making products based on perfluorooctanyl sulfonate (PFOS) chemistry.[30]

Vehicles and equipment

Because time decides survival, ARFF crews cannot first set up a water supply. Hydrants near runways count as obstructions and must stand well away, and underground hydrants are slow to open.[25] The crews therefore bring their water, in tanks of 3790 to 17,000 L (1000 to 4500 gal) with foam concentrate in proportion. The standards call for a double shot of foam, enough to discharge two full water tanks without refilling the foam tank. For 11,360 L (3000 gal) of water and 3 % AFFF, one tank uses 341 L (90 gal) of concentrate, so a double shot is 681 L (180 gal). The example vehicle in the handbook carries 1590 L (420 gal).[25]

ARFF vehicles are a special class of fire apparatus, designed to NFPA 414 rather than to the standard for structural apparatus.[31] NFPA 414 covers major firefighting vehicles, rapid intervention vehicles that reach the scene first to start rescue, and combined-agent vehicles.[32] For off-road use the weight is spread equally over all wheels, every wheel is driven, and clearances and acceleration exceed those of standard apparatus. In the United States, vehicles funded by the FAA must comply with Advisory Circular 150/5220-10D.[25]

Separate water and foam pumps let the turrets and the nozzles under the vehicle discharge while it moves.[33] Turrets deliver 1900 to 5700 L/min (500 to 1500 gpm), depending on vehicle size. The limited supply is meant to open a passage to the aircraft for rescue, not necessarily to put the whole fire out.[33] Low-attack turrets below the windscreen have proved more effective than roof turrets.[20] Non-air-aspirating AFFF turrets reach further than aspirating ones and are very effective on large hydrocarbon pool fires.[34]

Airport fire vehicle discharging foam from its turret onto a training fire
An ARFF vehicle discharging foam from its turret during training.

Piercing nozzles put agent into the fuselage without opening a door, which would admit air to the fire.[20] They are used by hand on attack lines or mounted on a high-reach extendible turret (HRET) controlled with a joystick from the cab.[20][35] Twinned-agent nozzles discharge dry chemical from an upper nozzle to knock down the flames and AFFF from a lower nozzle to secure the fuel against reflash.[36] For category 7 the minimum is two vehicles under ICAO, two to three under the FAA and three under NFPA 403. An airport that keeps only the minimum has no reserve for maintenance, repairs or training.[20]

Response time requirements

Time is the most important single factor in survival, and the 2008 handbook compares the FAA, ICAO and NFPA response times.[20] Under the ICAO Annex 14 edition it cites, the standard was no more than three minutes to any point of each operational runway in optimum visibility and surface conditions, with a recommendation of two minutes.[37] Further vehicles were to arrive within one minute of the first, so that agent application was continuous. NFPA 403 required the first vehicle to reach any point on the operational runway within 2 minutes and any point of the on-airport rapid response area within 2½ minutes. Further vehicles had to follow at intervals of no more than 30 seconds.[6]

The rapid response area extends 152 m (500 ft) on either side of the runway centreline and 503 m (1650 ft) beyond each runway end, within the airport boundary.[6] NFPA 402 describes a similar critical rescue and fire-fighting access area as long as the runway plus 2012 m (6600 ft), because survivable accidents tend to occur near the runway and threshold lights.[2] Under 14 CFR Part 139 at least one vehicle must reach the midpoint of the farthest air carrier runway and begin applying agent within three minutes of the alarm. All other required vehicles must do so within four minutes.[6]

Plan of a runway with a rectangle 152 m either side and 503 m beyond each end, and a longer access area of runway length plus 2012 m
Rapid response area of NFPA 403 and critical rescue and fire-fighting access area of NFPA 402 around a runway, as summarised in the 2008 handbook.

As reported in the 2008 handbook, the US government had not adopted NFPA 403 and had filed differences to ICAO Annex 14 on response time.[6] NFPA 403 also required equipment and personnel for interior firefighting to be at work within 5 minutes of notice of an accident.[2] More accidents occur in bad weather, which can lengthen response times, and NFPA 402 accepted that circumstances could make the times impossible to meet.[2]

Operations at the scene

Most ARFF responses to aircraft emergencies are precautionary. Many are announced minutes in advance by the control tower, with the aircraft type, the problem, the runway, the people and the fuel on board.[38] The vehicles then wait at standby positions chosen to reach a crash quickly, without grouping them where one skidding aircraft could hit them all. Emergencies without warning, such as an aborted take-off, require a direct response to the aircraft.[38]

Every arriving vehicle performs a quick size-up and reports smoke, fire, damage and fuel spills, which help the cockpit crew decide whether to evacuate.[38] Wind, slope, terrain, exposures, spilled fuel and the evacuation all have to be weighed within seconds when positioning the vehicles.[39] Transport aircraft must be certified for a full evacuation through half of the exits within 90 seconds. Fire fighters at the foot of the escape slides hold them steady in the wind, keep the escape area free of fire and lead passengers to safety. The slides are not fail-safe, and a collapsed landing gear, heat or wind can make them useless.[39]

Entry, search and interior attack start from the unburned side of the aircraft, with ventilation at the same time, because water on the fire quickly fills the cabin with smoke and steam.[39] The handbook treats an interior aircraft fire as an atmosphere immediately dangerous to life and health and calls for the US OSHA two-in/two-out rule and self-contained breathing apparatus.[40] Tyres at 1.7 MPa (250 psi) and pressure vessels at 21 MPa (3000 psi) or more are further hazards, and damaged composites can release harmful substances.[14]

Cargo aircraft carry the same fuel loads as passenger aircraft of the same size and often carry hazardous materials not allowed on passenger flights.[40] As the 2008 handbook described it, US Part 139 applied only to passenger operations, so an airport could handle Boeing 747 freighters all day without an FAA requirement for ARFF cover. Opening a cargo door can feed the fire without giving access, and skin-piercing nozzles guided by infrared cameras may then be the best tactic.[41]

Training, protective equipment and limits

Under 14 CFR Part 139, ARFF personnel must be trained before their first duty and receive recurrent training every 12 consecutive calendar months.[6] Each fire fighter must also take part in at least one live-fire drill that simulates an aircraft fire of the size typical for the airport index. Class 1 airports must hold a full-scale emergency exercise at least every 36 months.[42] The 2008 handbook reported that live-fire training with hydrocarbon fuels had been suspended at many airports because of environmental limits.[17] It also described increasing use of gas-fired props that simulate aircraft fires, while flammable liquid pits were declining because of groundwater contamination and black smoke.[43]

For clothing, a 1997 OSHA interpretation states that fire fighters whose primary job is crash and rescue must wear a proximity ensemble to NFPA 1971, the reflective silvers.[44] FAA Advisory Circular 150/5210-14B, mandatory for federally funded purchases, states that any hazard of high radiant heat from a fuel fire mandates proximity clothing.[38] Some departments with combined ARFF and structural duties question this, because many fire fighters find silvers stiff and cumbersome.[44]

The rules set minimums, and the handbook states that most ARFF departments do not have enough staff to carry out all tasks critical to survival in the time allowed.[45] Military-specification AFFF still meets the NFPA and FAA control criteria at rates 25 to 75 % below 5.5 L/min/m². That margin covers running fuel fires, debris that shields the fire and crosswinds that shorten the reach of foam streams.[46]

See also

Notes

  1. ↑ 1.0 1.1 Kreckie (2008), p. 13-99.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 Boucher (2008), p. 21-143.
  3. ↑ 3.0 3.1 3.2 3.3 3.4 Scheffey (2002), p. 4-103.
  4. ↑ 4.0 4.1 4.2 4.3 Kreckie (2008), p. 13-101.
  5. ↑ 5.0 5.1 5.2 5.3 Kreckie (2008), p. 13-102.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 6.5 Kreckie (2008), p. 13-107.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 Kreckie (2008), p. 13-103.
  8. ↑ Kreckie (2008), pp. 13-99–13-100.
  9. ↑ 9.0 9.1 Kreckie (2008), p. 13-100.
  10. ↑ Kreckie (2008), pp. 13-109–13-110.
  11. ↑ 11.0 11.1 Boucher (2008), p. 21-138.
  12. ↑ Van Rossum (2027), §4.1.
  13. ↑ 13.0 13.1 Conley (1965), as cited in Kreckie (2008), p. 13-101.
  14. ↑ 14.0 14.1 Boucher (2008), p. 21-142.
  15. ↑ 15.0 15.1 15.2 15.3 Kreckie (2008), p. 13-114.
  16. ↑ 16.0 16.1 Boucher (2008), p. 21-136.
  17. ↑ 17.0 17.1 Boucher (2008), p. 21-144.
  18. ↑ Boucher (2008), pp. 21-143–21-144.
  19. ↑ 19.0 19.1 Kreckie (2008), p. 13-104.
  20. ↑ 20.0 20.1 20.2 20.3 20.4 20.5 Kreckie (2008), p. 13-106.
  21. ↑ 21.0 21.1 21.2 Scheffey (2002), p. 4-101.
  22. ↑ Scheffey (2002), pp. 4-100–4-101.
  23. ↑ Iqbal and Salley (2004), p. 3-3.
  24. ↑ Scheffey (2002), p. 4-102.
  25. ↑ 25.0 25.1 25.2 25.3 25.4 25.5 Kreckie (2008), p. 13-105.
  26. ↑ Iqbal and Salley (2004), p. 3-4.
  27. ↑ Iqbal and Salley (2004), p. 3-2.
  28. ↑ Gottuk and White (2002), pp. 2-311–2-312.
  29. ↑ 29.0 29.1 Scheffey (2008), p. 17-46.
  30. ↑ Scheffey (2008), p. 17-69.
  31. ↑ Wieder (2008), p. 13-23.
  32. ↑ Tutterow (2008), p. 12-280.
  33. ↑ 33.0 33.1 Scheffey (2008), p. 17-64.
  34. ↑ Scheffey (2008), p. 17-59.
  35. ↑ Tutterow (2008), p. 12-276.
  36. ↑ Scheffey (2008), p. 17-65.
  37. ↑ Kreckie (2008), pp. 13-106–13-107.
  38. ↑ 38.0 38.1 38.2 38.3 Kreckie (2008), p. 13-109.
  39. ↑ 39.0 39.1 39.2 Kreckie (2008), p. 13-110.
  40. ↑ 40.0 40.1 Kreckie (2008), p. 13-111.
  41. ↑ Kreckie (2008), pp. 13-111–13-112.
  42. ↑ Kreckie (2008), pp. 13-107–13-108.
  43. ↑ Acomb and LeBoeuf (2008), p. 12-250.
  44. ↑ 44.0 44.1 Kreckie (2008), p. 13-108.
  45. ↑ Kreckie (2008), p. 13-113.
  46. ↑ Scheffey (2002), pp. 4-102–4-103.

References

  • Acomb, D. J., & LeBoeuf, R. M. (2008). Fire rescue stations and fire service training centers. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-233–12-251). National Fire Protection Association.
  • Boucher, B. (2008). Aviation. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-135–21-149). National Fire Protection Association.
  • Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-297–2-316). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Kreckie, J. (2008). Aircraft rescue and fire fighting (ARFF). In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 13-99–13-115). National Fire Protection Association.
  • Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-88–4-122). National Fire Protection Association; Society of Fire Protection Engineers.
  • Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
  • Tutterow, R. (2008). Fire department apparatus and equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 12-267–12-287). National Fire Protection Association.