Contents
Mass timber is structural wood used in large load-bearing sections or panels. Examples include glued-laminated timber (glulam) beams and cross-laminated timber (CLT) panels. A building may use a few deep beams and columns where a lightweight timber frame would use many slender members. The difference matters in fire because the dimensions of the wood remaining beneath the heated surface influence how much load it can carry.[1][2][3]
Exposed timber can contribute energy to a compartment fire at the same time as its cooler core continues to support a load. These are two distinct questions for structural fire engineering. One concerns how the fire develops in a room. The other concerns the strength of an individual beam, column or connection as the exposure continues.[2][4][3]

From the exposed face to the core
Heating breaks down the wood at the surface. Combustible gases escape, and a layer of char forms. The char has little load-bearing capacity and slows heating of the wood behind it. The timber just inside the char front can already be hot enough to have lost some strength. Oxidation at a solid surface can also continue without visible flames as smouldering. An assessment of timber in fire therefore considers both the lost section and the properties of the wood that remains.[5][3][6]
A one-face charring estimate
For a broad face exposed to a standard furnace fire, a constant charring rate gives a first estimate of the depth converted to char. White reports a commonly used approximation of 0.6 mm/min across the grain for the ASTM E119 standard exposure. Taking 30 minutes as an illustrative exposure gives an estimated char depth of 18 mm on that face.[5]
| Symbol | Meaning | Unit |
|---|---|---|
| Depth measured from the original face to the char front | mm | |
| Assumed linear charring rate | mm/min | |
| Duration of the assumed exposure | min |
The example assumes that the same face is exposed throughout. Corners, multiple exposed faces and changes in the fire exposure affect the remaining section. The reduced cross-section method can make a further allowance for heated wood beneath the char. The fire resistance of the assembly also depends on the load and the capacity of its connections.[5][3]
Exposed surfaces and fire load
Furniture and contents form part of the variable fire load. Exposed structural wood can also contribute to the permanent fire load. The distinction matters when using tabulated fuel loads for the contents of a room. The Australian verification data sheets identify the combustion of construction elements, including timber panels, as a possible contribution during a compartment fire.[2][4]
Members, panels and the building
The fire assessment of a high-rise building can involve both the load path through timber connections and the behaviour of extensive exposed surfaces. New Zealand’s C/VM2 (2025) illustrates the distinction in its interior-linings scenario. It lists specified structural timber members among the surface-finish exceptions, but excludes exposed panels on the underside of a floor or ceiling from that particular exception.[3][7]
See also
Notes
- ↑ Willse (2008), §19.1, pp. 19-8–19-9.
- ↑ 2.0 2.1 2.2 Australian Building Codes Board (2020), Data Sheet B1, pp. 7, 23, citing McGregor (2013).
- ↑ 3.0 3.1 3.2 3.3 3.4 White (2002), ch. 4-11, pp. 4-265–4-268.
- ↑ 4.0 4.1 Van Rossum (2027), §4.4.
- ↑ 5.0 5.1 5.2 White (2002), ch. 4-11, pp. 4-260–4-261.
- ↑ Ohlemiller (2002), ch. 2-9, pp. 2-200–2-201.
- ↑ Ministry of Business, Innovation and Employment (2025), §4.7, p. 50.
References
- Australian Building Codes Board. (2020). Fire safety verification method: Data sheets.
- Ministry of Business, Innovation and Employment. (2025). C protection from fire: Verification method C/VM2 (2nd ed.). New Zealand Government.
- Ohlemiller, T. J. (2002). Smoldering combustion. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
- White, R. H. (2002). Analytical methods for determining fire resistance of timber members. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Willse, P. J. G. (2008). Types of building construction. In A. E. Cote (Ed.), Fire protection handbook (20th ed.). National Fire Protection Association.