Contents
Boilover is the sudden ejection of burning oil from a tank when water beneath the hot oil turns to steam. It can follow a long period of apparently steady burning at the surface. Certain crude oils have the combination of light and heavy fractions needed for this to happen. The water can be a separate layer at the tank bottom or mixed into the bottom oil as an emulsion.[1][2]
While the fuel remains inside the tank, the walls define the area of the pool fire. Boilover can carry burning liquid over the rim and start a spill fire outside that boundary. The change in the area on fire is one reason a tank that has burned steadily for hours can still present a changing hazard.[3][1]
How heat reaches the water
A crude oil contains components with different boiling points. The lighter components evaporate preferentially at the burning surface. In oils susceptible to boilover, some of the remaining hot, denser liquid sinks and mixes with the cooler oil below. A hot layer develops beneath the surface.[1]
The lower boundary of this hot layer can advance downwards faster than the surface recedes. The surface burning rate alone therefore tells little about the distance between the hot oil and the water. When the hot layer reaches water, expanding steam can form a persistent froth with the viscous oil and carry it out of the tank.[1]
Boilover, slopover and frothover
The distinction depends on where the water is heated and whether the oil is already burning. In a boilover, water beneath the burning oil supplies the steam. In a slopover, water reaching the hot surface of a burning viscous oil causes frothing near that surface. In a frothover, water boils beneath hot viscous material, such as asphalt, and the container may overflow even in the absence of fire.[4]
The tank fire at Tacoa
In 1982 a fuel-storage tank supplying a power station at Tacoa, Venezuela, burned for about six hours before a violent boilover. The length of that burning period belongs to this particular incident. A view of a flame above a tank, even a large fireball, cannot establish the water and oil conditions beneath the surface.[4][1]
Surface protection
Firefighting foam acts at the fuel surface. A coherent blanket can restrict the escape of flammable vapour, and aqueous film-forming foam can also spread a film on hydrocarbon fuels. The foam blanket and the subsurface hot layer describe different parts of the tank. Establishing the condition of one requires different evidence from establishing the condition of the other.[5][1]
See also
Notes
References
- Gottuk, D. T., & White, D. A. (2002). Liquid fuel fires. In P. J. DiNenno (Ed.), SFPE handbook of fire protection engineering (3rd ed.). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program (NUREG-1805). U.S. Nuclear Regulatory Commission.
- Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote (Ed.), Fire protection handbook (20th ed.). National Fire Protection Association.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote (Ed.), Fire protection handbook (20th ed.). National Fire Protection Association.