A flame arrester is a device that stops a flame from passing through a flammable gas-air mixture. It does so by quenching the flame on the surfaces of an array of small passages, and the gases that emerge are cooled enough not to ignite the mixture on the protected side.[1] Unlike active isolation systems, which act only after an explosion has been detected, flame arresters are passive devices: the gas flow itself passes through narrow channels in which a flame is quenched.[2][3] They are used on the vents of tanks for flammable liquids, on process vents and pipelines, on small containers and inside gas detectors.[2][4][5][6]
The principle rests on the quenching distance of a mixture, the largest gap through which a flame cannot propagate.[7] An arrester at the end of a vent pipe, close to the likely ignition source, meets the flame before it can accelerate. One mounted inside a long pipe may face an accelerating deflagration or even a detonation, and needs special design and testing.[2] Arresters are suitable for gases and vapours, not for dusts or saturated vapours, and they can fail when they are clogged, damaged or heated by a long-burning flame.[2][4] In the language of explosion protection, the flame arrester is one of the passive methods of explosion isolation.[2]
Principle: quenching in narrow passages
A flame that tries to pass through a gap that is too small is quenched. According to Simmons (2002), quenching is probably due to a combination of heat loss to the walls and the removal of the free radicals that the flame needs in order to propagate.[7] The quenching distance is the largest gap that will just prevent propagation of a flame through the mixture. It is usually measured with spark ignition between a pair of parallel plates or with a rectangular burner.[7]
Flame arresters, called flame traps by Simmons (2002), use this effect. Stopping the flame front is not enough, however: any hot gas forced through the trap must also be cooled enough not to ignite a flammable mixture on the far side.[7] Beyler (2002b) makes the same point for enclosures, noting that hot quenched flame gases that expand through an opening may autoignite outside.[8]
The Fire Protection Handbook describes the practical form: the gas flow is made to pass through small passageways, so that flame propagation is prevented by thermal quenching.[2] In plate and tube arresters, heat from the outside flame is absorbed by the metal, which quenches the flame and prevents ignition of the vapours inside a tank.[4] The same quenching idea also governs explosion-proof enclosures for electrical equipment. Their joints are made narrow enough that a flame inside loses sufficient heat in the opening to be quenched.[9]
Quenching distance and safe gap
The quenching distance is often found by placing a pair of flanged electrodes in the gas mixture and trying to ignite it. If the mixture ignites, the plate separation is larger than the quenching distance.[8] The quenching distance between parallel plates is 65 % of the quenching diameter in a circular tube.[8] For a number of hydrocarbon-air mixtures, Beyler (2002b) relates the parallel-plate quenching distance to the minimum ignition energy with a simple correlation:
| Symbol | Description | Unit |
|---|---|---|
| Minimum spark ignition energy of the mixture in air | mJ | |
| Quenching distance between parallel plates, in air | mm |
The data behind the correlation cover minimum ignition energies from about 0.002 to 20 mJ and quenching distances from about 0.2 to 20 mm.[8] It shows why a mixture that is easy to ignite is also hard to quench: a low ignition energy goes together with a small quenching distance. Beyler (2002b) adds that the maximum experimental safe gap (MESG) of most hydrocarbons is about half the quenching distance.[8] The MESG is the gap through which a flame cannot pass, and it can be measured in a device such as the Westerberg explosion test vessel.[2]
Worked example. Methane can be ignited by as little as 0.3 mJ of electrical energy.[10] The correlation then gives mm between parallel plates. In a circular tube, the quenching diameter is mm, and the MESG is roughly half the parallel-plate value, about 1.1 mm. This suggests passages of the order of a millimetre for such a mixture, although passage length also governs the performance of an arrester.[4] The correlation is approximate; for arresters, the handbook refers to test requirements such as those of ANSI/UL 525.[8][2]
The MESG is also used to group flammable gases. NUREG-1805 classifies gases by MESG, determined by IEC test 79-1A (1975). It lists acetylene in Group A, hydrogen in Group B, ethylene in Group C and propane in Group D, citing Senecal (1997).[11] Hydrogen and acetylene also burn much faster than propane: their maximum laminar burning velocities in air are 320 and 175 cm/s, against 68 cm/s for ethene and 41 cm/s for propane.[12]
Flame propagation in pipes
The duty of an arrester depends on how fast the flame arrives. A flame moving along a duct away from an opening usually proceeds at first at a fairly uniform speed. This speed is controlled by the burning velocity of the mixture and the area of the flame front:[7]
| Symbol | Description | Unit |
|---|---|---|
| Linear speed of the flame along the duct | m/s | |
| Burning velocity of the mixture, relative to the unburnt gas | m/s | |
| Area of the flame front | m² | |
| Cross-sectional area of the duct | m² |
Because the flame front is always larger than the duct cross-section, typically by a factor of two or three, the flame travels faster than the burning velocity.[7] For a propane-air mixture with a maximum laminar burning velocity of 41 cm/s, the initial flame speed is therefore about 0.8 to 1.2 m/s. For hydrogen-air, at 320 cm/s, it is about 6.4 to 9.6 m/s.[12][7]
This steady phase does not last if the hot products cannot vent. They push the flame and the unburnt gas forward, which creates turbulence ahead of the flame and raises the burning velocity further.[7] Turbulence can roughly double the burning velocity of propane, ethene and acetylene flames at a Reynolds number of 40,000, and theory suggests a factor of five at very high turbulence.[12] In a long enough duct, the flame front acts as an accelerating piston, a shock wave forms, and the flame becomes a detonation travelling at typically 1500 to 3000 m/s.[7] For gases initially at atmospheric pressure, the pressure behind the detonation can reach 20 bar, and up to 100 bar where it reflects from the end of the duct.[7]
Ural and Garzia (2008) describe the same chain for process plants. A pipe that carries a flammable mixture can act as a fuse: ignition at one end can send a flame through the pipe to a process unit at the other end.[2] The flame speeds up steadily unless it is blocked near the point of ignition. In the detonable range the front can undergo deflagration-to-detonation transition, with pressures of about 25 times the initial pressure and reflected pressures up to 50 times.[2]
For a pipe initially at 101 kPa, these factors mean about 2.5 MPa and 5.1 MPa absolute.[2] These values are of the same order as the 20 bar and 100 bar given by Simmons (2002), although the reflected values differ by a factor of two.[7] Zalosh (2008) adds that most accidental explosions are deflagrations, but that detonations can follow a strong ignition source, an elongated or obstructed geometry, or very high turbulence.[13]
The difference matters for protection. In a deflagration the flame moves well below the speed of sound and the pressure rises almost uniformly; in a detonation the flame is supersonic and the pressure rises almost instantly behind a shock.[14] The Chapman-Jouguet detonation pressure is roughly twice the closed-vessel deflagration pressure, 16 to 20 atmospheres for a near-stoichiometric mixture at atmospheric pressure.[14] Explosion vents placed on a pipe can limit pressure and flame speed, yet the flame may still run through the whole length of pipe at moderate speed.[2] Pipeline detonations often cause periodic ruptures along the line, with each break acting as a pressure relief before the pressure builds up again.[15]
Types of arrester
The Fire Protection Handbook distinguishes static dry flame arresters from hydraulic, or liquid seal, arresters.[2] Approved dry arresters are cellular. They include perforated-plate, parallel-plate, crimped-metal-ribbon and sintered metal arresters.[4] Two parameters govern their effectiveness: the diameter or width of the flame passages and their length.[4] Arresters built from banks of parallel metal plates or tubes, with a large metal surface to dissipate heat, are more effective than screens for larger openings and less subject to clogging and corrosion.[16][4]
Wire screens are a special case. A screen of 40 mesh has 40 wires per 25.4 mm in each direction, and each opening has an area of about 0.14 mm².[4] Such a screen will ordinarily stop a flame passing through small openings, but it cannot be relied on as a flame arrester. Its wires can be damaged and its mesh can clog with dirt or other residues.[4] In gas detectors, catalytic sensors sit inside a flame arrester of wire mesh or sintered metal, so that combustion on the hot sensor bead cannot spread to the atmosphere outside.[5]
A hydraulic arrester passes the gas through a liquid, which breaks the flow into single bubbles that rise by buoyancy. Because the bubbles are isolated, no continuous channel exists through which a flame can pass.[17] The device blocks a flame that starts on the side where the bubbles reach the liquid surface, which is the usual direction of use. For ignition on the upstream side, the protection is less effective, because combustion can be transferred to the surface of the liquid.[17] Designs include bubble-screen and sparge-tube vessels with instruments for gas flow, liquid level and temperature.[3]
By position, arresters are of the end-of-line type, at the outlet of a vent pipe, or the in-line type, mounted within the pipe.[4] Flame arresters are normally placed at the end of a pipeline near a possible ignition source. Arresters intended for use at a significant distance from the pipe end, such as in-line units, are subject to special requirements, and NFPA 69 contains requirements for their installation.[2] The US Coast Guard set test requirements for arresters in mid-pipe positions that may be challenged by a detonation, and these were adopted in ANSI/UL 525, Standard for Safety Flame Arresters.[2][18]
Applications
The main use is on the vents of tanks for flammable liquids. In US practice described by Ordile (2008), every tank needs a vent for filling, emptying and thermal expansion and contraction; API Standard 2000 gives the design basis. Alternatively, the normal vent should be at least as large as the largest fill or withdrawal connection, and never less than 32 mm (1.25 in.).[16] Approved pressure-vacuum (breather) vent valves or flame arresters on the vent pipes prevent flashback into the tank. These devices are required when a flammable mixture is present and for the storage of all Class I liquids.[16] NFPA 30, as summarised in the 2008 handbook, also requires normally closed vents for Class IA liquids, with a flash point below 73 °F (22.8 °C) and a boiling point below 100 °F (38 °C).[16]
On an atmospheric storage tank that holds a liquid whose flash point lies in the range of normal summer temperatures, the vapour space normally contains a flammable mixture. Flame arresters have their most important application on such tanks.[4] Lightning protection guidance in the same handbook lists, among its conditions for metal tanks of flammable liquids, that all vapour openings are closed or fitted with flame arresters for Class I liquids.[19] More generally, Benedetti (2008) names safe venting of storage tanks, and flame arresters that guard against flame travelling into the storage, among the design means for flammable liquid storage.[20]
Smaller containers use the same idea. Scarbrough (2008b) describes the practice in spray finishing. Flammable liquid containers of more than 19 L (5 gal) kept indoors should have a special plug that combines a pressure relief valve, a vacuum relief valve and a flame arrester.[6] Containers of coating materials near process areas should have pressure relief devices and flame arresters at all openings.[6] For small quantities the handbook prefers the safety can, whose spring-closed caps prevent spills and act as an emergency vent in a fire.[21] Process tanks for dipping are drawn with a vent fitted with a flame arrester.[22]
Other uses are found in engines, boats and process plants. Arcing electrical parts of stationary combustion engines that pump or compress flammable liquids or gases should be safeguarded by flashover shielding, flame arresters, purging or ventilation.[23] On US boats with gasoline engines, as described by Eberly (2008), backfire flame arresters are still required, although they no longer need a US Coast Guard approval number.[24] A backfire arrester in fully premixed air-fuel gas piping stops flame propagation, shuts off the fuel and relieves the pressure of a backfire.[25] In oilseed solvent extraction plants, the absorber vent discharges to the atmosphere through a flame arrester.[26]
Limitations and maintenance
A flame arrester is only as good as its passages. Condensation, crystallisation of some liquids and freezing of moisture in winter can make conservation vents and flame arresters impractical, and steam tracing is sometimes provided to prevent this.[4] If an arrester is exposed to a long-burning flame, the metal plates can become hot enough on the tank side to ignite the flammable vapour-air mixture inside.[4] Arresters are not suitable for dust or saturated vapour service.[2] In oxygen-enriched atmospheres, above 21 % oxygen by volume or an oxygen partial pressure above 21.27 kPa (160 mmHg), the arresters of gas sensors may need a special design.[5]
Arresters are not fitted everywhere. In US oilseed extraction plants, NFPA 36 as described by Kingsbaker (2008) requires relief valves on the extraction vessels, and their discharge line to the atmosphere must not be fitted with a flame arrester.[26] The handbook's comparison of isolation methods shows the trade-off. A flame arrester isolates a deflagration and an ignition source in gas service, but it does not provide flow or pressure isolation; a liquid seal behaves in the same way.[27]
The flame arrester is therefore one option among several. For dusts, or where pressure must also be stopped, Ural and Garzia (2008) describe rotary valves, flame front diverters, float valves and active systems with fast-acting valves or chemical barriers.[2][27] Each of these isolation techniques has its own application limits.[2]
See also
Notes
- ↑ Iqbal and Salley (2004), p. F-30.
- ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 Ural and Garzia (2008), p. 17-158.
- ↑ 3.0 3.1 Ural and Garzia (2008), p. 17-161.
- ↑ 4.00 4.01 4.02 4.03 4.04 4.05 4.06 4.07 4.08 4.09 4.10 4.11 4.12 Ordile (2008), p. 7-19.
- ↑ 5.0 5.1 5.2 Cholin (2008a), p. 14-103.
- ↑ 6.0 6.1 6.2 Scarbrough (2008b), p. 9-33.
- ↑ 7.00 7.01 7.02 7.03 7.04 7.05 7.06 7.07 7.08 7.09 7.10 Simmons (2002), p. 1-147.
- ↑ 8.0 8.1 8.2 8.3 8.4 8.5 Beyler (2002b), p. 2-182.
- ↑ Beyler (2002b), p. 2-181.
- ↑ L. J. Moore (2008), p. 9-214.
- ↑ Iqbal and Salley (2004), p. B-24.
- ↑ 12.0 12.1 12.2 Simmons (2002), p. 1-146.
- ↑ Zalosh (2008), p. 2-100.
- ↑ 14.0 14.1 Zalosh (2008), p. 2-99.
- ↑ Zalosh (2002), p. 3-411.
- ↑ 16.0 16.1 16.2 16.3 Ordile (2008), p. 7-18.
- ↑ 17.0 17.1 Ural and Garzia (2008), p. 17-160.
- ↑ Ural and Garzia (2008), p. 17-165.
- ↑ Caloggero (2008), p. 11-78.
- ↑ Benedetti (2008), p. 6-7.
- ↑ Ordile (2008), p. 7-31.
- ↑ Katunar (2008), p. 9-40.
- ↑ Biggins (2008), p. 8-107.
- ↑ Eberly (2008), p. 21-156.
- ↑ Iqbal and Salley (2004), p. F-7.
- ↑ 26.0 26.1 Kingsbaker (2008), p. 9-135.
- ↑ 27.0 27.1 Ural and Garzia (2008), p. 17-159.
References
- Benedetti, R. P. (2008). Fire hazards of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-3–6-9). National Fire Protection Association.
- Beyler, C. L. (2002b). Flammability limits of premixed and diffusion flames. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-172–2-187). National Fire Protection Association; Society of Fire Protection Engineers.
- Biggins, J. B. (2008). Stationary combustion engines and fuel cells. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-105–8-111). National Fire Protection Association.
- Caloggero, J. M. (2008). Lightning protection systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 11-69–11-81). National Fire Protection Association.
- Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
- Eberly, R. (2008). Marine vessels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 21-151–21-185). National Fire Protection Association.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Katunar, J., III (2008). Dipping and coating processes. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-39–9-51). National Fire Protection Association.
- Kingsbaker, C. L. (2008). Oilseed solvent extraction plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-131–9-140). National Fire Protection Association.
- Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
- Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
- Scarbrough, D. R. (2008b). Spray finishing and powder coating. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-27–9-37). National Fire Protection Association.
- Simmons, R. F. (2002). Premixed burning. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 1-144–1-154). National Fire Protection Association; Society of Fire Protection Engineers.
- Ural, E. A., & Garzia, H. W. (2008). Explosion prevention and protection. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-141–17-165). National Fire Protection Association.
- Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.
- Zalosh, R. (2008). Explosions. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-93–2-106). National Fire Protection Association.