Fse-stair-pressurisation-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 11 KB)

Summary

Pressure difference between a pressurised 20-storey stair and the building, with −10 °C outside and 21 °C in the stair.

Original vector illustration for Stair pressurisation, level 2 Intermediate.

  • Alt text: Line chart: pressure difference between stair and building rising in a straight line from 20 Pa at the bottom to 106 Pa at the top of a 66 m stair.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.