Skip to content
From Fire Safety Academy Wiki
Revision as of 09:28, 13 November 2026 by Mark (talk | contribs) (Remove source references from file description)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-sprinkler-skipping-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 20 KB)

Summary

Calculated temperature of a standard response sprinkler link in a 1,000 kW fire, without droplets and with liquid volume fractions of 1 and 2 millionths in the ceiling jet.

Original illustration for Sprinkler skipping, level 4 Expert.

  • Alt text: Line chart: link temperature rising towards 88 °C; it reaches 74 °C at 174 s without droplets, 234 s and 361 s with droplets.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:32, 2 November 2026Thumbnail for version as of 17:32, 2 November 2026900 × 600 (20 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity