Skip to content
From Fire Safety Academy Wiki
Revision as of 09:28, 13 November 2026 by Mark (talk | contribs) (Remove source references from file description)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-sprinkler-skipping-v1.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)

Summary

How skipping arises: small droplets from the first operating sprinkler are carried up by the plume and along the ceiling jet, where they strike and cool the link of the next sprinkler.

Original illustration for Sprinkler skipping, level 4 Expert.

  • Alt text: Cross-section of a room: a fire plume rises under an operating sprinkler; the ceiling jet carries droplets to a second sprinkler that stays closed.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:31, 2 November 2026Thumbnail for version as of 17:31, 2 November 2026900 × 600 (9 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity