Fse-froude-scaling-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 7 KB)

Summary

Critical velocity to stop smoke backflow in a corridor at full scale and in a 1/4 scale model, from Thomas's relation.

Original illustration for Froude scaling, level 4 Expert.

  • Alt text: Two corridors in side view: full scale 1.22 m wide with 150 kW fire and 1.45 m/s airflow; model 0.31 m wide, 4.7 kW, 0.73 m/s.