Summary

Mass flow at the design level 3 m above the balcony (6 m above the fire) for the worked example, by method.

Original illustration for Balcony spill plume, level 4 Expert.

  • Alt text: Bar chart of plume mass flow 6 m above a 5 MW fire: in the open 26.0, line plume 34.2, Milke's equation 62.9 and Cooper's alternative 68 kg/s.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:33, 2 November 2026Thumbnail for version as of 17:33, 2 November 2026900 × 600 (8 KB)Jan (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity