Fse-transformer-fire-v4.svg (SVG file, nominally 864 × 940 pixels, file size: 19 KB)
Summary
Radiant heat flux from a 5 m² transformer oil pool fire (8950 kW) by the point source model, for radiative fractions of 0.30 and 0.60. Based on Iqbal and Salley (2004), p. 5-3; Budnick et al. (2008), p. 3-150; Nowlen et al. (2005b), p. H-1.
Original illustration for Transformer fire.
- Alt text: Radiant heat flux versus distance from a 9 MW transformer oil pool fire for radiative fractions 0.30 and 0.60, with cable damage criteria
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.