Summary

Trench effect in the cited gas-burner channel experiments: flames attached above 15° inclination; on the 30° King's Cross escalator, with sidewalls, a fire across the full width lay down in the trench, while a fire across one third of the width rose vertically. Based on Alpert (2008), p. 2-25, and Cox and Kumar (2002), pp. 3-207–3-208.

Original illustration for Escalator fire protection.

  • Alt text: Diagram of flames detached on a flat surface but attached along a 30 degree walled escalator trench, as at King's Cross

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current13:11, 12 November 2026Thumbnail for version as of 13:11, 12 November 20261,000 × 1,360 (8 KB)Peter (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file: