Summary

Heat release rate of a 400 L diesel spill, confined in a 2.0 m² curb or spread unconfined over concrete, with a small diked spill from NUREG-1805 for scale. The unconfined value ignores ventilation limits.

Original illustration for Stationary combustion engine.

  • Alt text: Bar chart of heat release rate for a 400 L diesel spill: 3.9 MW confined in a 2 m2 curb versus about 56 MW unconfined