Summary

Hydrogen concentration in a ventilated battery room with a release of 0.538 ft³/min and an air flow of 100 ft³/min, for perfect mixing, compared with the 1 percent limit.

Original illustration for NFPA 69.

  • Alt text: Curve of hydrogen concentration rising towards 0.54 percent over five air changes, below the 1 percent limit line