Skip to content
From Fire Safety Academy Wiki
Revision as of 08:47, 9 November 2026 by Emma (talk | contribs) (Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-purged-and-pressurised-enclosure-v3.svg (SVG file, nominally 900 × 660 pixels, file size: 11 KB)

Summary

Hexane concentration in a perfectly mixed enclosure against the number of purge volumes: the lower flammable limit is reached after about 1.75 volumes, and 10 volumes leave about 3 ppm.

Original illustration for Purged and pressurised enclosure.

  • Alt text: Line chart of hexane concentration against purge volumes on a log scale, falling from 6.9 percent to about 3 ppm after 10 volumes

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current08:47, 9 November 2026Thumbnail for version as of 08:47, 9 November 2026900 × 660 (11 KB)Emma (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata