An atmospheric storage tank is a tank for flammable or combustible liquids that is designed to operate at or close to atmospheric pressure. In the classification described in the Fire Protection Handbook (2008), atmospheric tanks are designed for gauge pressures from 0 to 1.0 psig (0 to 6.9 kPa), below low-pressure tanks and pressure vessels.[1] Common forms are horizontal cylindrical tanks, vertical cone roof tanks and tanks whose roof floats on the liquid.[1] According to Ordile, its hazard depends less on its size than on the liquid stored, the tank design, its foundation and supports, its vents and its piping.[2] Spilled liquid must also be kept from reaching other tanks.[3] Tank fires may begin with an explosion in the vapour space or with a spill fire, and a long fire in an open-top tank of crude oil can end in a violent boilover.[4][5] The rules summarised here come mainly from the US code NFPA 30 and from American Petroleum Institute (API) standards as described in the 2008 handbook, so they show US practice around 2007–2008.
Definition and pressure classes
The handbook divides storage tanks into three classes of pressure design. Atmospheric tanks are designed for 0 to 1.0 psig (0 to 6.9 kPa) and low-pressure storage tanks for 1.0 to 15 psig (6.9 to 103 kPa). Pressure vessels are designed for more than 15 psig (103 kPa).[1] The unit psig means pounds per square inch of gauge pressure, the pressure above the surrounding atmosphere. Pressure tanks and pressure vessels are mainly used to limit vapour loss from liquids with a high vapour pressure.[1]
Other documents set the upper limit lower. The glossary of the US Nuclear Regulatory Commission report NUREG-1805 (2004) quotes the NFPA online glossary. It defines an atmospheric tank as a storage tank designed to operate at gauge pressures from atmospheric through 0.5 psi (3.45 kPa).[6] The limit therefore depends on the document and its edition. The SFPE Handbook speaks of "fixed or cone roof atmospheric storage tanks" for tanks with a roof fixed to the shell, without giving pressure limits.[7]
Ordile stresses that the size or number of tanks matters less than several other factors. These are the properties of the stored liquid, the tank design, its foundation and supports, the size and location of its vents, and its piping.[2] Storage in sound, well-maintained tanks should also be less dangerous than transferring the liquid. Storage involves no active steps in which human error can cause a spill.[2]
Tank types and construction
The handbook shows five common atmospheric tank types. The horizontal tank is a cylinder lying on its side, and the ordinary cone roof tank is a vertical cylinder with a fixed conical roof. In a floating roof tank the roof deck rests on the liquid and moves with the liquid level. A lifter roof tank has a liquid-sealed roof that rises with the vapour volume, and a vapour dome tank has a flexible diaphragm inside a hemispherical roof.[1] The floating roof type is treated in the article Floating-roof tank.
According to Ordile, aboveground tanks should be built of steel or concrete unless the liquid demands another material, because both resist the heat of an exposure fire. Tanks of materials with a low melting point may fail and spread the fire.[8] The shell thickness covers the strength needed to hold the liquid plus an allowance for corrosion. It is checked periodically by visual, magnetic particle, ultrasonic or radiographic inspection.[8] For vertical welded atmospheric tanks, API Standard 650 may be used to calculate the minimum shell plate thickness. The nominal thickness is the greater of the design thickness and the hydrostatic test thickness, but never less than the values below.[8]
| Nominal tank diameter | Minimum nominal thickness |
|---|---|
| Smaller than 50 ft (15.2 m) | 3/16 in. (4.8 mm) |
| 50 ft to, but not including, 120 ft (15.2 to 36.6 m) | 1/4 in. (6.4 mm) |
| 120 to 200 ft inclusive (36.6 to 61.0 m) | 5/16 in. (7.9 mm) |
| Over 200 ft (61.0 m) | 3/8 in. (9.5 mm) |
Concrete tanks require special engineering. Unlined ones should only store liquids of 40 degrees API gravity or heavier, and lined ones may be used for other liquids.[9] Aboveground secondary containment tanks have become increasingly popular. In these, a primary steel tank is enclosed by a second steel or fibreglass tank, or by a geomembrane shell, which holds any leak. Many are also encased in 152 mm (6 in.) of reinforced concrete against exposure fires and vandalism.[1] Ordile links their popularity to the US federal rules for the underground storage tank.[1]
Vapour space and flammability
The gas space above the liquid, the vapour space, decides whether an internal explosion is possible. Where the liquid has a vapour pressure above 28 kPa (4 psia, absolute), as gasoline does, the vapour space is normally too rich to burn.[1] It can enter the flammable range if the gasoline is at −23 to −46 °C (−10 to −50 °F). Part of it can also become flammable when air enters during emptying or a sudden cooling rainstorm, and stratification can keep it so for hours or days.[1]
For liquids with a vapour pressure below about 14 kPa (2 psia), such as kerosene, the vapour space is normally too lean to burn. It becomes flammable only if the whole body of liquid is heated to its flash point, for example by an exposure fire.[1] The temperature of the liquid, not of the vapour space, decides whether a flammable mixture forms. Ethyl and methyl alcohol and JP-4 (Jet B) turbine fuel have vapour pressures of about 14 to 28 kPa at 38 °C (2 to 4 psia at 100 °F). Their vapours are normally in the flammable range, so the handbook calls floating roof tanks or inert gas in the vapour space desirable for them.[1]
Temperature also changes the liquid volume. Gasoline expands by about 0.07 % for each 10 °F (6 °C) rise in ordinary atmospheric temperatures, and acetone and ethyl ether expand more. Tanks should therefore not be filled completely.[2] Aboveground tanks are often painted white or aluminium to reflect heat, which slows the rise in liquid temperature and the evaporation of the contents.[2]
Normal and emergency venting
Every atmospheric tank needs a normal vent for filling, emptying and thermal expansion and contraction. API Standard 2000 gives the sizing basis. Alternatively, the vent should be at least as large as the largest filling or withdrawal connection and never smaller than 32 mm (1.25 in.) nominal inside diameter.[9] A clogged or undersized vent can rupture the tank by pressure or collapse it by vacuum. Hazardous vented vapour is piped to a safe outside point at least 3.7 m (12 ft) above grade.[9]
As described in the 2008 handbook, NFPA 30 requires normally closed vents for Class IA liquids. These have a flash point below 22.8 °C (73 °F) and a boiling point below 37.8 °C (100 °F).[10] Pressure-vacuum (breather) vent valves or flame arresters are required where a flammable mixture is present and for all Class I liquids.[9] A 40-mesh wire screen cannot be relied on as a flame arrester, because the wires can be damaged or clogged.[11]
Emergency venting deals with a fire under or around the tank, which can otherwise raise the internal pressure until the tank explodes.[12] Relief can come from loose manhole covers, a weak roof-to-shell seam, rupture disks, remote vapour depressuring or a pressure relief device.[12] Horizontal tanks under excessive pressure usually fail at the ends. In a vertical cone roof tank, a weak roof-to-shell seam lifts and gives adequate relief. Cone roof tanks under 6 m (20 ft) in diameter may need extra venting to protect the shell-to-bottom seam, while a floating roof removes the need for emergency venting.[12]
The required capacity depends on the wetted area, the inside surface wetted by a full tank that a ground fire can expose. It is 55 % of the exposed area of a sphere, 75 % of that of a horizontal tank, and the lowest 9 m (30 ft) of shell of a vertical tank.[12] Table 7.2.2 of the handbook gives the required venting in "free air" at 101 kPa and 15.5 °C. Values run from 597 m³/h for 1.86 m² to 21,011 m³/h for 260 m² (742,000 ft³/h for 2,800 ft²), with interpolation between rows.[13]
The table reflects the probable heat transfer per unit area, the exposed share of the tank, and the time to boil the contents or weaken dry steel.[12] Beyler notes that most heat flux measurements on objects engulfed in pool fires were made to set tank venting. He takes 120 kW/m² as a reasonable, conservative maximum time-averaged flux.[14]
For any stable liquid, the handbook corrects the tabulated rate with the latent heat of vaporisation and the molecular weight of the liquid. The required rate falls as either property rises. In SI units the correction is:[13]
For tanks designed above 1 psig (6.9 kPa) with more than 260 m² (2,800 ft²) of wetted area, the handbook adds a power law. It rests on a heat absorption of Btu/h with A in ft².[13]
| Symbol | Description | Unit |
|---|---|---|
| Required venting in free air at 101 kPa and 15.5 °C, from Table 7.2.2 or the power law | m³/h | |
| Required venting for the specific stable liquid | m³/h | |
| Latent heat of vaporisation of the liquid | kJ/kg | |
| Molecular weight of the liquid | – | |
| Exposed wetted area (power law only: tanks above 1 psig and 260 m²) | m² |
As described in the 2008 handbook, NFPA 30 allows one reduction factor per tank. It is 0.5 for approved drainage on tanks with more than 18.6 m² (200 ft²) of wetted area and 0.3 for approved water spray with drainage, approved automatic water spray or approved insulation. Approved water spray with approved insulation gives 0.15.[13] With some restrictions the factors may be halved for liquids that burn no more intensely than ethanol, but never below 0.15.[13]
Worked example. Consider an aboveground horizontal tank 2.44 m in diameter and 8.23 m long, the 8 ft by 27 ft size that the handbook lists for a 37,854 L (10,000 gal) underground tank.[4] The shell and both ends give π × 2.44 × 8.23 + 2 × π × 2.44²/4 = 72.4 m², and 75 % of this is a wetted area of 54.3 m² (584 ft²).[12] Table 7.2.2 lists 10,024 m³/h at 46.45 m² and 11,100 m³/h at 55.74 m². Interpolation gives 10,932 m³/h, rounded up to 11,000 m³/h (about 388,000 ft³/h) of free air.[13] With approved drainage, the factor 0.5 lowers this to about 5,500 m³/h.
Siting, supports and spill control
As described in the 2008 handbook, NFPA 30 sets distances from tanks to property lines, public ways and important buildings. They depend on whether the tank pressure can exceed 2.5 psig (17 kPa), including in a fire, and on whether the liquid is stable, unstable or prone to boil-over. Tank size, exposure protection and extinguishing systems also count, and NFPA 30 sets the spacing between tanks.[9]
Vertical tanks are normally set on a slightly raised concrete pad that keeps the bottom out of standing water. Exposed pilings or steel supports should have a fire resistance rating of at least 2 hours.[3] A common fire starts at a tank vehicle loading next to tanks on unprotected steel legs. The supports fail, the tanks drop, and their piping breaks or the tanks rupture. Loading racks should therefore be at least 7.6 m (25 ft) from tanks for Class I liquids and 4.6 m (15 ft) for Class II and III liquids.[3]
Where a release could endanger important facilities, waterways or neighbouring property, the spill must be controlled. The most desirable method is sloping ground with dikes or ditches that lead the liquid away from all tanks into an impounding basin. Otherwise, dikes of earth, concrete, solid masonry or steel surround the tanks, and intermediate dikes at least 457 mm (18 in.) high stop small spills reaching other tanks.[3] A dike should hold the greatest amount that the largest tank can release, assumed full. The volume of other tanks below the top of the dike counts as unavailable.[3]
Dike drain valves are kept closed and placed outside the dike. Dikes higher than 1.8 m (6 ft) need extra measures for access and escape. Class I dikes averaging over 3.6 m (12 ft), or walls closer to a tank than they are high, need valve and roof access from above the dike top. Vapour can collect in the narrow space between tank and wall.[3] Secondary containment tanks within the capacity limits of NFPA 30 need no dike.[3]
Worked example. The SFPE Handbook design example uses a vertical cone roof gasoline tank 36.6 m (120 ft) in diameter and 14.6 m (48 ft) high.[15] Full, it holds π/4 × 36.58² × 14.63 = 15,372 m³. Alone in a dike 1.83 m (6 ft) high, it needs a dike floor of at least 15,372/1.829 = 8,406 m², rounded up to 8,410 m². This includes the tank's own footprint of 1,051 m² and corresponds to a square of about 92 m on each side. A second tank in the enclosure would add its own footprint to this area, because its volume below the dike top is unavailable.[3]
Fire scenarios
Storage tank fires may originate with an internal explosion or with a spill fire exposing the tanks.[4] A spill fire is a pool fire on the ground or in the dike. Slye notes that it grows until it burns as fast as liquid is released. At a burning rate of 0.3 m/h, each 3.8 L/min of spillage gives an equilibrium area of about 0.74 m².[16] The shell above the liquid level must be cooled, or the steel can overheat, bulge and rupture however good the venting is.[3] Failed piping and valves have also added their contents to ground fires, so cast iron, aluminium, copper and brass should not be used.[3]
Internal explosions occur when the vapour space reaches the flammable range, most readily with liquids whose flash point is near the storage temperature. They have also occurred in exposure fires with liquids whose flash point was above the storage temperature. The fire heated the liquid, and a hot part of the shell ignited the vapours.[4] In a prolonged fire, the shell of a large vertical tank tends to fold inwards above the burning liquid without splitting.[4]
A boilover can follow when the roof of a tank holding certain crude oils is blown off, or a floating roof sinks. After a long period of quiet burning, part of the oil is suddenly ejected.[5] Slye names three conditions that must all be present. There must be free water or a water-oil emulsion at the tank bottom. The oil must have a wide boiling range, so that a hot residue of 149 °C (300 °F) or more sinks as a "heat wave". Finally, enough heavy oil must be present to form a tough froth of oil and steam.[5][16]
The worst loss-of-life tank fire in NFPA records, at Tacoa, Venezuela, on 19 December 1982, ended in a boilover after 6 hours of burning. It killed 160 people, 50 of them fire fighters.[16] The NUREG-1805 glossary likewise requires water at the bottom of an open tank for boilover.[17]
Fire protection with foam
Fixed or cone roof atmospheric tanks can be protected with fire fighting foam, applied by monitors, handlines, fixed outlets on the shell or subsurface injection.[7][18] As summarised in the SFPE Handbook (2002), NFPA 11 accepts monitors as primary protection only for fixed roof tanks under 18.3 m (60 ft) in diameter. Handlines suit only tanks under 9 m (30 ft) in diameter and no higher than 6 m (20 ft).[7] Fixed foam chambers sit just below the top rim, with frangible seals that keep vapour out of the foam piping.[19]
Topside application has known weaknesses. An explosion can damage the foam makers, and the fire updraft can stop foam reaching the surface. On tanks larger than about 61 m (200 ft) in diameter, foam from the rim may not seal the centre.[20] NUREG-1805 lists the same problems.[21] Subsurface injection avoids them by pumping foam in near the tank bottom, from where it rises through the fuel. The handbook recommends it only for cone roof tanks with hydrocarbon fuels, and the SFPE Handbook excludes Class IA liquids.[20][18]
The SFPE design example shows the supply involved. The 36.6 m gasoline tank has a liquid surface of 1,051 m² (11,310 ft²). At the minimum rate of 0.1 gpm/ft² (4.07 L/min per m²) for hydrocarbons, it needs 1,132 gpm (about 4,290 L/min) of foam solution.[15] NFPA 11 sets 55 minutes of discharge for gasoline with Type II outlets. With a 3 % concentrate this gives 34 gpm × 55 min = 1,870 gal (about 7,080 L) of concentrate.[22]
Scope and limitations
The requirements above come from the Fire Protection Handbook (2008) and the SFPE Handbook (2002), which describe US codes as they stood at the time. Ordile cites API 650 in its 10th edition (1998) and API 2000 in its 5th edition (1998), but lists NFPA 11 and NFPA 30 without an edition.[23] Later editions may differ, and other countries regulate tank storage with their own codes. Even the pressure limit of an atmospheric tank differs between the sources.[1][6] The tabulated venting rates are design values derived from assumed heat input, exposed area and heating times, not a model of a particular fire.[12]
See also
Notes
- ↑ 1.00 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 Ordile (2008), p. 7-16.
- ↑ 2.0 2.1 2.2 2.3 2.4 Ordile (2008), p. 7-15.
- ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 Ordile (2008), p. 7-22.
- ↑ 4.0 4.1 4.2 4.3 4.4 Ordile (2008), p. 7-23.
- ↑ 5.0 5.1 5.2 Slye (2008), p. 6-205.
- ↑ 6.0 6.1 Iqbal and Salley (2004), p. F-5.
- ↑ 7.0 7.1 7.2 Scheffey and Hickey (2002), p. 4-126.
- ↑ 8.0 8.1 8.2 Ordile (2008), p. 7-17.
- ↑ 9.0 9.1 9.2 9.3 9.4 Ordile (2008), p. 7-18.
- ↑ Slye (2008), p. 6-198.
- ↑ Ordile (2008), p. 7-19.
- ↑ 12.0 12.1 12.2 12.3 12.4 12.5 12.6 Ordile (2008), p. 7-20.
- ↑ 13.0 13.1 13.2 13.3 13.4 13.5 Ordile (2008), p. 7-21.
- ↑ Beyler (2002a), p. 3-290.
- ↑ 15.0 15.1 Scheffey and Hickey (2002), p. 4-130.
- ↑ 16.0 16.1 16.2 Slye (2008), p. 6-206.
- ↑ Iqbal and Salley (2004), p. F-9.
- ↑ 18.0 18.1 Scheffey and Hickey (2002), p. 4-127.
- ↑ Scheffey (2008), p. 17-60.
- ↑ 20.0 20.1 Scheffey (2008), p. 17-61.
- ↑ Iqbal and Salley (2004), p. B-61.
- ↑ Scheffey and Hickey (2002), p. 4-131.
- ↑ Ordile (2008), p. 7-33.
References
- Beyler, C. L. (2002a). Fire hazard calculations for large, open hydrocarbon fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-268–3-314). National Fire Protection Association; Society of Fire Protection Engineers.
- Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
- Ordile, A. M. (2008). Storage of flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-15–7-33). National Fire Protection Association.
- Scheffey, J. L. (2008). Foam extinguishing agents and systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-45–17-70). National Fire Protection Association.
- Scheffey, J. L., & Hickey, H. E. (2002). Foam system calculations. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 4-123–4-148). National Fire Protection Association; Society of Fire Protection Engineers.
- Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-197–6-208). National Fire Protection Association.