Fse-silane-v4.svg (SVG file, nominally 1,240 × 740 pixels, file size: 12 KB)

Summary

Average silane concentration in a well-mixed, ventilated enclosure for a leak of 1.18 L/s (0.25 mm orifice, 103.4 bar), calculated with the dilution balance, with the lower flammable limit of 1.0 percent and 25 percent of it.

Original illustration for Silane.

  • Alt text: Line chart: average silane concentration falls from above 1 percent to 0.17 percent as exhaust flow rises from 50 to 708 L/s; LFL line at 1 percent.