Summary
Ignition data for an XLPO/XLPO communications cable in the fire propagation apparatus. The inverse square root of the ignition time is linear in the heat flux; the slope gives TRP = 537 kW·s½/m² and the intercept the critical heat flux of 19.9 kW/m².
Original illustration for Fire propagation apparatus.
- Alt text: Scatter plot of four ignition points for an XLPO cable on a straight line crossing zero at 19.9 kW/m², slope giving TRP of 537.