Skip to content
From Fire Safety Academy Wiki
Revision as of 08:30, 8 November 2026 by Linda (talk | contribs) (Remove bibliographic source lines from image captions and descriptions)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-mattress-flammability-v3.svg (SVG file, nominally 1,270 × 740 pixels, file size: 6 KB)

Summary

Simulated-bedclothes exposure in the United States open-flame mattress test (16 CFR 1633): a T-head burner of 18 kW above the top surface and one of 9 kW beside the side. Pass limits: peak heat release rate 200 kW, 15 MJ in the first 10 minutes.

Original illustration for Mattress flammability.

  • Alt text: Side and top views of a mattress on its foundation with an 18 kW T-burner above the top and a 9 kW T-burner beside the side.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current07:55, 8 November 2026Thumbnail for version as of 07:55, 8 November 20261,270 × 740 (6 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata