Skip to content
From Fire Safety Academy Wiki
Revision as of 08:29, 8 November 2026 by Linda (talk | contribs) (Remove bibliographic source lines from image captions and descriptions)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-spill-fire-v1.svg (SVG file, nominally 1,220 × 820 pixels, file size: 13 KB)

Summary

Small unconfined spills on concrete lose heat to the floor and can burn at about one-fifth of a deep pool's rate per unit area. The depths shown are conservative estimates; large continuous spills may approach pool rates.

Original illustration for Spill fire.

  • Alt text: Cross-sections of a thin unconfined spill on concrete losing heat downward and of a deeper confined pool inside a curb, each with flames above.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current08:06, 8 November 2026Thumbnail for version as of 08:06, 8 November 20261,220 × 820 (13 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity
07:41, 8 November 2026Thumbnail for version as of 07:41, 8 November 20261,220 × 730 (13 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata