A corner fire is a fire that burns at or against the junction of two walls, usually meeting at 90°, often with a ceiling above. The term covers both a burning item placed in a room corner and the burning of combustible wall linings that form the corner.[1][2] Corner fires are more severe than fires against a flat wall or in the open. The two walls restrict the air drawn into the flames, so the flames become longer and the plume hotter. The walls also exchange radiation with each other and with the flame.[3][2]

On combustible surfaces the effect is strongest. Upward flame spread near a 90° wall intersection is roughly three times faster than on a flat wall.[4] Fires in the corner of a room lined with a combustible material spread flame faster and reach flashover sooner than fires elsewhere in the room.[5] For this reason the corner is the standard ignition position in room fire tests for wall and ceiling linings, such as ISO 9705 and NFPA 286.[6][7] In fire engineering calculations, the reduced air entrainment of a corner fire is commonly represented by treating it as one quarter of a fire four times as large.[8][9]

Configuration

For combustible surfaces larger than about 1 m in height or width, the behaviour of a fire is determined mainly by the configuration of the burning surface. That configuration sets the flame shape, the heat transfer from the flame and the rate at which flame spreads to new fuel.[10] Alpert (2008) distinguishes pools, walls, ceilings, inclined surfaces, parallel surfaces, ducts and the ceiling-corner configuration. In the last of these, vertical combustible surfaces meet at 90° (a corner) or 180° (a flat wall) and are combined with a ceiling.[1]

This combination occurs in nearly every room and corridor, and inside building fixtures and equipment.[1] In the terminology of NUREG-1805, a fire located in a compartment corner, where the walls typically meet at 90°, produces a corner flame.[2] The corner may contain a separate burning item, such as a waste basket or a chair. Alternatively, the walls themselves may be combustible interior finish that ignites and becomes the main fuel. Most test methods and correlations distinguish between these two cases: an exposure fire against inert walls, and burning walls.[5][11]

An interior corner, where the walls enclose the fire on two sides, must not be confused with an exterior corner, where the fire stands outside the angle of two walls. Smoke production methods treat the two differently.[12] An interior corner restricts entrainment far more than an exterior corner does.[12]

Why corner fires grow faster

The first mechanism is reduced air entrainment. A fire in the open draws air into its plume from all directions. Near a wall or in a corner, the amount of entrained air falls, which gives higher temperatures and velocities and a smaller volume of gases.[8] According to NUREG-1805, the reduced entrainment lengthens the flames and makes the plume hotter at a given height than it would be in the open.[3]

The second mechanism is radiative reinforcement. The corner traps thermal radiation from the flames and from hot, charred surfaces, much as two parallel surfaces do when a fire starts at their base.[1] NUREG-1805 attributes the greater severity of corner fires compared with wall fires to the radiative heat exchange between the two burning walls. The physical processes controlling fire growth in the two cases are otherwise very similar.[2]

The third mechanism is the nature of upward flame spread. On a vertical surface, the flame heats the material above the burning zone, mainly by radiation, and that material ignites after a delay set by its thermal inertia.[13] The rate at which flame height increases is proportional to the current flame height. Flame height therefore grows exponentially, with a constant doubling time, which is why burning vertical surfaces are so hazardous.[13]

Van Rossum (2027) gives the same explanation in simpler terms: the material above the burning part is preheated, so the fire spreads faster.[14] A survey by Mitler and observations by Saito showed that upward spread near a 90° wall intersection is roughly three times faster than on a flat wall. Radiative reinforcement and the induced air flow that holds the flame in the corner explain the difference.[4]

When the corner flames reach a ceiling, the pattern changes. The flames spread fastest along the junction of wall and ceiling, forming a "T" shape that quickly involves the upper walls far from the point where the flames struck the ceiling.[4] Once the walls at the corner and along the ceiling burn, further spread is slower. It proceeds sideways from the corner and downwards from the ceiling by the creeping, opposed-flow mechanism also seen on floors.[4] With a noncombustible ceiling, flames also spread downward, but combustible walls give much more rapid spread because of the heat exchange between them.[15]

Isometric corner with ceiling: flames rise up the corner, spread sideways along the top of both walls in a T shape, then creep down and outwards.
Flame spread in a corner with a ceiling: upward spread in the corner is about three times faster than on a flat wall; at the ceiling the flames run along the wall-ceiling junction in a T shape, after which slower creeping spread proceeds sideways and downwards.

Some materials show this behaviour in an extreme form. Cellular plastics that resist burning under most exposures have behaved very differently when their surfaces faced each other and exchanged radiant heat. Low thermal conductivity, a high heat release rate and rapid degradation produced a fast upward flame front in a room corner. When the ceiling was insulated with the same exposed foam, the fire spread rapidly across its underside, even from a fire as small as a waste basket.[16] Such behaviour of foam plastic insulation led to the use of large corner tests, described below.[17]

Heat fluxes in a corner

The heat flux that a corner fire imposes on its walls and ceiling has been measured with propane burners against noncombustible corners. Lattimer et al. used square burners with sides of 0.17, 0.30 and 0.50 m and fires of 25 to 300 kW. They developed correlations for the walls in the corner, the top of the walls and the ceiling.[5] The peak heat flux along the height of the walls depends on the burner side length:[5]

q˙′'peak=120[1−exp⁡(−4.0D)]

Heights in the corner are scaled with the flame tip length. This length follows from a dimensionless heat release rate based on the side of the burner. Both are defined as follows:[5]

Lf,tipD=5.9(QD*)1/2,QD*=Q˙ρ∞cpT∞gD5/2

Symbols in the corner heat flux correlations
Symbol Description Unit
q˙′'peak Peak incident heat flux on the walls in the corner kW/m²
D Side length of the square fire source m
Lf,tip Flame tip length of the corner fire m
QD* Dimensionless heat release rate –
Q˙ Heat release rate of the fire kW
ρ∞,cp,T∞ Density, specific heat and temperature of ambient air kg/m³, kJ/(kg·K), K
g Acceleration due to gravity m/s²

The heat flux peaks in the lower part of the flame, up to about 40 % of the flame tip length, and decreases above it.[5] Along the top of the walls and on the ceiling, the correlations level off at 120 kW/m² close to the corner, the maximum expected from the flame itself.[5][18] Sideways along the wall, the heat flux falls with the actual distance from the corner, because the entrained air pushes the fire into the corner. Whether these correlations hold for sources larger than 0.50 m per side has not been established.[5]

Curve rising from 0 to about 110 kW/m² as burner side grows to 0.7 m, approaching a dashed 120 kW/m² line; points at 0.17, 0.30 and 0.50 m.
Peak heat flux on the walls of a corner as a function of the side length of a square fire source, from the correlation of Lattimer et al. for propane fires of 25 to 300 kW.

Inside a room, the hot gas layer adds to the flux from the flame. In an ISO 9705 room with a 300 kW fire on a 0.17 m burner, heat fluxes in the upper part of the room rose by up to 20 kW/m² compared with the fire alone. The upper gas temperature was then about 680 K.[19] The position of the fire matters as well. A 40 kW fire against the corner walls was attached to them and gave up to 50 kW/m². When it was moved 50 mm away, the flames detached and the highest flux fell to about 25 kW/m².[19]

Burning corner walls produce higher heat fluxes than a burning flat wall. In tests with L-shaped burners simulating burning walls in a 2.4 m high corner with a ceiling, peak fluxes of about 70 kW/m² were measured over the lower half of the flame. Other experiments gave 28 to 38 kW/m² with L-shaped burners in an open corner, and about 33 kW/m² in the lower half of a burning PMMA corner.[11]

Plume entrainment and flame height

Engineering correlations for plumes and ceiling jets assume a fire away from walls. For fires against walls they are adjusted by the method of reflection, which uses symmetry to account for the air that the walls block. For a fire against a flat wall, twice the heat release rate is substituted; for a fire in a 90° corner, four times the heat release rate is used.[20][8] The idea is that the corner fire behaves like one quarter of an imaginary fire with four times its heat release rate. Its plume mass flow is therefore one quarter of the mass flow of that four-times-larger fire.[9]

Plan views of a fire in the open, against a wall and in a corner, with air arrows and dashed mirror fires behind the walls.
Air is entrained from all sides by a fire in the open (left), from half its perimeter against a wall (centre) and from a quarter in a 90° corner (right). In the method of reflection the walls are replaced by mirror-image fires, giving 2Q for a wall and 4Q for a corner.

The handbook expresses the same idea with a wall factor in the plume entrainment equation used in NFPA 92B. The factor is smaller the more the walls enclose the fire. The mass flow of smoke at a height above the fuel is:[12]

m˙=0.071k2/3Q˙c1/3z5/3+0.0018Q˙c

Symbols in the plume entrainment equation and wall factors
Symbol Description Unit
m˙ Mass flow in the plume at height z kg/s
k Wall factor: 1 with no nearby walls, 3/4 near an exterior corner, 1/2 against a wall, 1/4 in an interior corner –
Q˙c Convective heat release rate, often taken as 0.7 times the total heat release rate kW
z Height above the top of the fuel m

The equation assumes that the flame tip lies well below the smoke layer and that the fire is roughly as long as it is wide. It also assumes a ceiling high enough to ignore the virtual origin.[12] The average temperature rise of the plume follows from ΔT=Q˙c/(m˙cp), with a specific heat of about 1.00 kJ/(kg·K).[21] With k = 1/4, the first term of the equation equals the mirror-image result of Van Rossum (2027).[9]

Flame height in a corner has also been correlated directly. NUREG-1805 gives a correlation by Hasemi and Tokunaga, based on a large number of fire tests. It relates the corner flame height to the heat release rate alone:[15]

Hf,corner=0.075Q˙3/5

Here Hf,corner is the corner flame height in metres and Q˙ the heat release rate in kW. The correlation estimates the length of flame along the junction of the walls and the radiation from it to objects in the room.[15] Like the other flame height correlations in NUREG-1805, it was obtained from laboratory-scale fires.[22]

Worked example

A fire of 1,000 kW burns in a tall space, and the smoke flow is needed 10 m above the fuel. With a convective fraction of 0.7, the convective heat release rate is 700 kW.[21] For a fire away from the walls (k = 1), the entrainment equation gives:

m˙=0.071×7001/3×105/3+0.0018×700≈30.5 kg/s

For the same fire in an interior corner (k = 1/4), the factor k2/3 is 0.397, and the mass flow falls to about 12.9 kg/s. The average temperature rise of the plume becomes about 54 K instead of about 23 K. The corner fire thus produces about 42 % of the smoke mass of the free fire at that height, but that smoke is more than twice as hot.[12][21] The corner flame height correlation above gives about 4.7 m for this fire, well below 10 m, so the equation is used within its assumptions.

Line chart of plume mass flow against height for a 1 MW fire: highest in the open, lower against a wall, lowest in a corner.
Plume mass flow against height above the fuel for a 1,000 kW fire (700 kW convective) in the open (k = 1), against a wall (k = 1/2) and in an interior corner (k = 1/4).

The corner flame height correlation can be applied to the burner of the ISO 9705 test. At 100 kW the corner flame height is about 1.19 m, and at 300 kW about 2.30 m.[15] The second value is comparable to the 2.4 m height of the standard test room.[7] For the 0.17 m square burner used in the ISO 9705 studies reviewed by Lattimer (2002), the peak heat flux correlation gives 120 × (1 − e−0.68) ≈ 59 kW/m² on the walls of the corner.[5][19]

Corner fires in fire testing

Laboratories began testing wall and ceiling linings in corner configurations around 1970. They built corners 2.44 m (8 ft) high, with short wing walls, a ceiling of the same material and a wood crib at floor level as ignition source.[17] Concern about rapid flame spread over cellular plastics with low tunnel ratings in real fires reinforced the use of the corner test. Factory Mutual Research and Underwriters Laboratories used corners up to 7.6 m (25 ft) high with wing walls up to 15.4 m (50 ft) long to study cellular plastics and protective measures.[17]

In tests at Underwriters Laboratories, a 9.1 kg (20 lb) wood crib in a full-size corner had about the same severity as the 88 kW tunnel burner and imposed about 11 kW/m² (1.1 W/cm²). Four materials with the same tunnel flame spread classification of 18 behaved very differently in the corner. A fire-retardant polyurethane spray foam affected 85 % of the wall and ceiling area, against 24 to 37 % for the other three.[23]

Modern room corner test methods place a gas burner in the corner opposite the door. In ISO 9705, used in New Zealand to classify linings, the room is 3.6 m long, 2.4 m wide and 2.4 m high with a 2.0 m by 0.8 m opening in one short wall.[7] The burner provides 100 kW for 10 minutes and then 300 kW for 10 minutes.[24] In NFPA 265 the burner stands 51 mm from each wall and provides 40 kW, then 150 kW, while in NFPA 286 it stands flush against both walls and provides 40 kW, then 160 kW.[25][6] The European Single Burning Item test uses the same geometry at a smaller scale: two vertical wings 1.5 m high form a corner and are exposed to a 30 kW propane burner.[26]

Corner fires also appear in tests of other fire protection products. The fire tests of UL 1626 and FM 2030 for residential sprinklers simulate a fire in the corner of a room furnished like a living room.[27] Large-scale venting experiments were run at IIT Research Institute in 1980 and 1981. Their fires were placed in a corner to represent one quarter of a larger fire in the centre of a 46 m by 15.2 m room.[28] In 75 residential sprinkler tests of 1979 and 1980, heat and toxic gases built up particularly fast when the fire started in the corner of a room or near curtains.[29]

Use in design

The choice of fire position in a design depends on what is being assessed. In New Zealand, Verification Method C/VM2 (first edition), as reproduced in the 2013 commentary, requires the design fire to be located away from walls and corners to maximise air entrainment into the plume.[30] The commentary explains the reasoning. A fire in the centre of the room entrains the most air, so the smoke layer descends fastest and detection is slowest. A fire against a wall or in a corner gives a hotter upper layer and a shorter time to reach the limiting thermal fractional effective dose. The design is usually governed by visibility, which requires the layer to descend below 2.0 m.[31]

The assessment of linings uses the corner deliberately. The Australian Fire Safety Verification Method data sheets base their reference scenario for wall and ceiling linings on an item burning in a room corner, closely aligned with ISO 9705.[32] The proportion of fires that start in corners and against walls can then be used to estimate conservatively how many fires the lining design fire applies to.[33]

Computer models handle corners only partly. Around 2007, most zone models approximated the effect of walls and corners on plumes, flame heights and ceiling jets with limited methods. Flame spread submodels using cone calorimeter and LIFT data were beginning to predict flame spread and heat release in wall and corner fires.[34] Hand methods have similar limits. NUREG-1805 states that its MQH correlation for the hot gas layer temperature, with its coefficient of 6.85, is not valid for a fire flush with a wall or in a corner.[35]

Limitations and misconceptions

The method of reflection works only when the fuel is truly in contact with both walls. Zukoski et al. found that a circular burner touching a wall at a single point behaved almost like a fire far from the wall. Its entrainment fell by only 3 %, so it should be represented by about 1.05 times its heat release rate, not twice.[20] The same caution applies in a corner, as the experiments with a burner moved 50 mm from the corner walls show.[19] A corner fire is therefore not simply any fire near a corner.

The sources also differ on how much a corner lengthens the flames. NUREG-1805 states that walls and corners lengthen flames, whereas a review by McCaffrey, cited by Heskestad (2002), reports the effects of walls and corners on flame height to be generally small.[3][36] Flame length also depends on its definition. Lattimer et al. define the flame tip as the furthest distance at which flaming is seen, which is longer than a mean flame height. For a 100 kW fire on a 0.17 m burner, the flame tip correlation gives about 2.75 m, against 1.19 m from the corner flame height correlation.[11][5][15]

The heat flux correlations were derived for steady propane fires against noncombustible walls, in corners about 2.4 m high and for sources up to 0.50 m per side.[5] In growing fires on combustible linings, the room environment and the burning walls add to these fluxes.[19][37] Finally, the corner is not the worst case for every question. It is the most severe position for flame spread over linings and for the temperature of the smoke, but a fire in the centre of a room produces more smoke and fills the room faster.[5][31]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 Alpert (2008), p. 2-26.
  2. ↑ 2.0 2.1 2.2 2.3 Iqbal and Salley (2004), p. 4-2.
  3. ↑ 3.0 3.1 3.2 Iqbal and Salley (2004), p. 4-1.
  4. ↑ 4.0 4.1 4.2 4.3 Alpert (2008), p. 2-28.
  5. ↑ 5.00 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 Lattimer (2002), p. 2-272.
  6. ↑ 6.0 6.1 Hirschler (2008b), p. 18-31.
  7. ↑ 7.0 7.1 7.2 Ministry of Business, Innovation and Employment (2013), p. 139.
  8. ↑ 8.0 8.1 8.2 Custer (2008), p. 2-57.
  9. ↑ 9.0 9.1 9.2 Van Rossum (2027), §6.7.
  10. ↑ Alpert (2008), p. 2-21.
  11. ↑ 11.0 11.1 11.2 Lattimer (2002), p. 2-285.
  12. ↑ 12.0 12.1 12.2 12.3 12.4 Milke and Klote (2008), p. 18-44.
  13. ↑ 13.0 13.1 Alpert (2008), p. 2-24.
  14. ↑ Van Rossum (2027), §4.3.
  15. ↑ 15.0 15.1 15.2 15.3 15.4 Iqbal and Salley (2004), p. 4-4.
  16. ↑ Benedetti and Colonna (2008), p. 6-225.
  17. ↑ 17.0 17.1 17.2 Hirschler (2008b), p. 18-29.
  18. ↑ Lattimer (2002), p. 2-273.
  19. ↑ 19.0 19.1 19.2 19.3 19.4 Lattimer (2002), p. 2-275.
  20. ↑ 20.0 20.1 Alpert (2002), p. 2-20.
  21. ↑ 21.0 21.1 21.2 Milke and Klote (2008), p. 18-45.
  22. ↑ Iqbal and Salley (2004), p. 4-5.
  23. ↑ Benedetti and Colonna (2008), p. 6-226.
  24. ↑ Hirschler (2008b), p. 18-32.
  25. ↑ Hirschler (2008b), p. 18-30.
  26. ↑ Hirschler (2008a), p. 6-48.
  27. ↑ Madrzykowski and Fleming (2008), p. 16-97.
  28. ↑ Heskestad (2008), p. 18-69.
  29. ↑ Hirschler (2008b), p. 18-39.
  30. ↑ Ministry of Business, Innovation and Employment (2013), p. 40.
  31. ↑ 31.0 31.1 Ministry of Business, Innovation and Employment (2013), p. 43.
  32. ↑ Australian Building Codes Board (2020a), Data Sheet B4, p. 48.
  33. ↑ Australian Building Codes Board (2020a), Data Sheet B4, p. 52.
  34. ↑ Beyler et al. (2008), p. 3-98.
  35. ↑ Iqbal and Salley (2004), p. 2-23.
  36. ↑ Heskestad (2002), p. 2-15.
  37. ↑ Lattimer (2002), p. 2-291.

References

  • Alpert, R. L. (2002). Ceiling jet flows. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-18–2-31). National Fire Protection Association; Society of Fire Protection Engineers.
  • Alpert, R. L. (2008). Physics of fire configuration. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-21–2-29). National Fire Protection Association.
  • Australian Building Codes Board. (2020a). Data sheets: Fire Safety Verification Method (Handbook annex, Print version 1.1).
  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • Beyler, C. L., DiNenno, P. J., Carpenter, D. J., & Watts, J. M., Jr. (2008). Introduction to fire modeling. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-93–3-110). National Fire Protection Association.
  • Custer, R. L. P. (2008). Dynamics of compartment fire growth. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-49–2-58). National Fire Protection Association.
  • Heskestad, G. (2002). Fire plumes, flame height, and air entrainment. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-1–2-17). National Fire Protection Association; Society of Fire Protection Engineers.
  • Heskestad, G. (2008). Venting practices. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-57–18-72). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lattimer, B. Y. (2002). Heat fluxes from fires to surfaces. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-269–2-296). National Fire Protection Association; Society of Fire Protection Engineers.
  • Madrzykowski, D., & Fleming, R. P. (2008). Residential sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-91–16-107). National Fire Protection Association.
  • Milke, J. A., & Klote, J. H. (2008). Smoke movement in buildings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-43–18-55). National Fire Protection Association.
  • Ministry of Business, Innovation and Employment. (2013). Commentary for Building Code clauses C1–C6 and Verification Method C/VM2.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.