Coal storage is the keeping of coal, a solid fuel burned mainly in boilers for steam and electricity, in outdoor piles, silos, bunkers and bins between delivery and use.[1] The main hazards of storing and handling it are fires, flash fires and dust explosions.[1] An important cause of fires in piles, bins and hoppers is spontaneous heating, the slow oxidation that builds up heat inside the coal until it ignites.[1] The risk is controlled mainly in two ways: by compacting the coal to reduce air movement through it, or by keeping it moving so that no portion stays in storage long enough to heat.[2] Once a fire has developed deep inside a silo or pile, it is hard to extinguish and may take days or weeks to put out.[3][4] Most of the guidance summarised here comes from the US Fire Protection Handbook (2008) and describes American practice around 2007–2008.

Coal as a stored fuel

Coal is ranked by ASTM D388 into four classes: anthracitic, bituminous, subbituminous and lignitic, each divided into groups.[2] The rank gives some indication of how readily a coal heats spontaneously and how severe its dust explosion hazard is.[1] Bituminous coals usually have heat values above 15,000 Btu/lb (34.9 MJ/kg), but they also contain sulfur in the form of pyrites.[1] To meet sulfur dioxide limits, more American power boilers began to burn subbituminous coals, which contain less sulfur but have lower heat values.[1] These "western" coals are mined in places such as Montana and Wyoming, and the Powder River Basin (PRB) deposits are one of the more common sources.[1] A data table in the International Fire Engineering Guidelines gives calorific values of 34 MJ/kg for anthracite and 31 MJ/kg for "coal, coke", against 18 MJ/kg for wood.[5]

Like wood, oil and gas, coal is combustible because of its high content of carbon and hydrogen.[6] Combustion can take two forms, flaming and smouldering.[7] According to Sheridan (2008), the principal hazards of coal at electric generating plants are its combustibility, spontaneous ignition and a tendency to produce fugitive dust. These hazards are more prevalent in the low-sulfur, low-rank coals such as PRB coal and lignite.[8] With PRB coal, spontaneous heating of spillage and dust is more common, which makes housekeeping and dust control especially important.[8]

The amount of fuel in a coal store is large. The fire load table in the same guidelines lists 2,500 MJ/m² for a coal bunker and 10,500 MJ/m² for a coal cellar.[9] Sheridan (2008) notes that American power plants were then tending to keep a 30 to 45 day supply, where 90 days or more used to be common.[8]

Spontaneous heating in stored coal

Spontaneous heating starts with a slow oxidation reaction within the coal. If the heat of oxidation builds up faster than it can dissipate, the temperature rises until the coal ignites; the handbook describes this as a problem of bituminous and lignite coals.[1][2] The NUREG-1805 glossary uses coal as one of its examples: spontaneous combustion may occur when combustible matter such as hay or coal is stored in bulk under conditions that do not let the heat dissipate.[10] A handbook table of materials subject to spontaneous heating rates the tendency of bituminous coal as moderate. It advises storing it in small piles and avoiding high temperatures, and remarks that high-volatile coals are particularly liable to heat.[11]

Dungan (2008b) lists eleven conditions that govern how susceptible a coal is to spontaneous heating.[2] The first group concerns the coal itself: how easily it breaks into fine particles, how well it absorbs oxygen, and its moisture content, since moisture assists oxidation. Its chemical composition also matters, and lower grades generally heat more readily. Sulfur in the form of pyrites or marcasites makes the coal more brittle, so that it breaks more easily and exposes more surface to oxidation. The second group concerns the pile: the air and free gases in its voids, and foreign matter such as wood, leaves and grass. The method and depth of piling, the surrounding temperature and the ventilation through the pile complete the list.[2]

The SFPE Handbook explains why pile size matters so much. Gray (2002) describes a critical condition that separates mild self-heating from runaway ignition. For a body of fixed size this condition is a critical ambient temperature; for storage of a variable amount at a constant temperature it is a critical size.[12] A larger body and a higher ambient temperature both favour ignition, because they reduce the rate of heat loss relative to heat generation. The centre of the body is hottest, so spontaneous ignition typically leaves a charred core inside an almost intact exterior.[13] Time to ignition grows with size: haystacks that are supercritical tend to ignite after a few weeks and coal stockpiles after a few months.[14]

Compacted and uncompacted piles

The way a pile is built, and the way silos, bins and bunkers are filled, has a large effect on the oxidation hazard. Dungan (2008b) names two ways of controlling it: compacting the coal to reduce air movement, or keeping the storage time short by moving the coal steadily to the boiler.[2] Uncompacted coal is coal that has been moved and has fallen on itself, as on conveyors, in trucks and rail cars, in bunkers and silos and in any "live" pile. At this density air fills roughly a third of the pile, so air can move through it fairly easily.[2]

Densities of coal, after Dungan (2008b)
Condition of the coal Density, lb/ft³ Density, kg/m³ (converted) Air in the pile
In the seam before mining 80–85 1,280–1,360 0 %
2 in. × 0 coal as loaded, no compaction 50–55 800–880 36 %
2 in. × 0 coal compacted with track-mounted dozers 60–65 960–1,040 24 %
2 in. × 0 coal compacted with rubber-tyred carryall or sheepsfoot roller 70–75 1,120–1,200 12 %

The imperial densities and the air percentages are those of the handbook.[2] The metric values were converted for this article, because the metric values printed in the handbook table do not match the imperial ones. The air percentages follow directly from the densities. For the uncompacted coal, 1 − 52.5/82.5 ≈ 0.36, so about 36 % of the pile volume is void, compared with 1 − 72.5/82.5 ≈ 0.12 for well compacted coal.

Compaction is done in layers 150 to 300 mm (6 to 12 inches) thick, each rolled by a machine with a high ground loading. Rubber-tyred carryalls are normally used, because they compact the coal while carrying it into place.[2] The pile should be compacted on all sides, so that no low-density zones remain. Air then occupies only about 12 % of the volume, and appreciable air movement through the pile becomes unlikely. Almost all types of coal have been stored this way, in piles of more than one million tons and nearly 30 m (100 ft) deep.[2] Large users such as utilities usually keep compacted permanent piles together with uncompacted live piles, while small users normally have only uncompacted storage.[2]

Large outdoor coal stockpile at a power station with a dozer or carryall working on top
Outdoor coal stockpile being worked by mobile equipment. Based on Dungan (2008b), p. 7-4.

Uncompacted piles on the ground need careful siting. The site should not lie over open sewers or other features that could bring air into the base of the pile, and it should not contain steam lines that could warm part of the pile.[15] Vegetation and foreign material are removed, and the ground is graded so that water drains away from the base. Because uncompacted piles tend to heat, the handbook advises shaping them for easy access to hot areas. It also suggests limiting their height to about 4.6 m (15 ft) when the coal is known to heat readily.[15] Greater heights can be tolerated for coals with low heating tendencies, provided the pile can be rotated easily.[15]

Segregation of coarse and fine coal is a further cause of heating. When coal is dropped into a conical pile, the coarse pieces roll to the outside and the fines collect in the centre. Air can then flow through the coarse coal to the fines, which have a large surface area.[15] Coal placed against a vertical wall or around supporting beams also tends to be less compacted, so the looser coal acts as a flue. Where walls cannot be avoided, the coal should be laid along the wall rather than pushed up against it.[15]

Coal for small users is often double-screened, with a top size of 32 mm (1¼ inches), a bottom size of 6 mm (¼ inch) and few fines. Such a pile is effectively fully ventilated and has little tendency to heat. Industrial users more often take coal with more fines and a top size of 50 mm (2 inches) or less.[15]

For piles that must be kept for long periods, the surface can be sealed with road tar. This excludes air so that a heated heap stops oxidising and cools, and it also reduces wind losses and channelling by rain.[15] Disturbance is a third option: Gray (2002) notes that coal stockpiles have long been rearranged from time to time with a front-end loader.[16]

Silos, bunkers and bins

Inside a plant, coal is held in silos of about 544 to 907 metric tonnes (600 to 1,000 tons) and in bunkers of up to about 4,540 tonnes (5,000 tons).[4] Ideally these are designed for mass flow, so that all the coal moves through them and no dead portion remains. The coal still oxidises slowly, but it leaves the system before appreciable heating can occur.[3] Outdoor piles can achieve the same effect when they are rotated on a first-in, first-out basis.[3]

Where mass flow cannot be achieved, the bottom of the store can be sealed as far as practical to restrict airflow through the coal. The space above the coal should not be sealed, however. It should be ventilated so that gases released from freshly mined or crushed coal cannot accumulate.[3] Heating in a bunker, silo or bin generally starts where static deposits of coal have remained for some time. For this reason the store may need to be drawn down and cleaned routinely, with special safety precautions for the cleaning work.[3] Sheridan (2008) adds that silos and bunkers should be emptied during plant outages to prevent spontaneous ignition.[4]

Methane and other gases can be liberated from freshly mined and crushed coal. Spontaneous heating produces carbon monoxide, which is both toxic and explosive.[15] Dangerous accumulations can form over the tops of bins, silos and bunkers and in underground reclaim tunnels. The handbook gives adequate ventilation as the best solution, with airflow swept across the tops of the stores and through the conveyor galleries. Where accumulation is suspected, fixed and portable monitors for carbon monoxide and methane are recommended.[15][17] Similar hazards of dust, methane and heating inside piles and silos occur at coal preparation plants at mines, and fires underground are treated in Mine fire.[18]

Detecting and fighting fires in stored coal

A fire caused by spontaneous heating is deep-seated. Gray (2002) notes that such burning is difficult to extinguish completely and can reignite days after it seemed to be out.[13] Hot spots can be found with carbon monoxide monitors, portable infrared detectors or thermography. Another method is a long thermocouple, about 3 m (10 ft), pushed into the coal and read on a portable instrument.[3][15] Repeated measurements show whether temperatures are rising and help with planning a response.[15]

Once a silo, bunker or bin is on fire, it is very difficult to extinguish the fire short of emptying the store, so a means of emptying it should be provided.[3] Fire fighting in coal silos can take several days, and Sheridan (2008) notes that such fires can last for weeks.[3][4] The handbook refers to NFPA 850, the US recommended practice for electric generating plants, for guidance on these fires. It describes several techniques.[3]

Carbon dioxide vapour has proved effective when it is forced under pressure into the upper and lower parts of a silo, at a rate that compensates for absorption by the coal.[3] The carbon dioxide is stored as a liquid and passes through an external in-line vaporiser.[3][19] The gas is first injected into the space above the coal to reduce the risk of an explosive atmosphere forming there. The main flow is then moved to the bottom, because the chimney effect in a silo stops the gas from settling throughout.[3]

Inerting is generally considered successful at a carbon dioxide concentration of 65 %. Reaching that level everywhere may need close to 100 % in most of the silo. The handbook therefore advises ordering about three times the gross silo volume of carbon dioxide when a low-pressure system is used.[3] For an illustrative silo with a gross volume of 1,200 m³ (a value chosen for this example), that rule gives about 3,600 m³ of carbon dioxide. Barriers and warning signs are needed where the gas could collect and deplete the oxygen around the silo.[3]

Nitrogen has also been used successfully. Because its density is close to that of air, it must be injected at many points, which needs more equipment and more agent.[3] Class A foam and penetrants have had some success. Coal plants have reported good results with Class A foam at 0.1 %, where it acts as a surfactant, whereas higher concentrations caused bubble accumulation that hindered penetration.[3]

Water and steam are not recommended for silo fires. Water reaching a hot spot can cause an explosion when the expanding steam is trapped, and steam adds heat and moisture that can increase spontaneous heating.[3] For PRB coal, a newer technique uses thermal imaging cameras to locate the hot spot and a piercing rod to apply micelle encapsulating agents.[4] Both chapters stress pre-fire planning and trained personnel. Dungan (2008b) states that crews should be trained at least to the structural fire brigade level of NFPA 600 and wear breathing apparatus. Sheridan (2008) adds that incipient fire brigades should not undertake this work.[15][4]

Coal dust and handling

Receiving operations, crushers and conveyors share a common hazard: the potential for a coal dust explosion.[17] The handbook gives a minimum explosive concentration for coal dust in air of 35 to 50 g/m³ (0.035 to 0.050 oz/ft³) and explosion pressures of 34.5 to 690 kPa (5 to 100 psi). Moisture has little effect on explosibility below about 10 %.[17] The main sources of dust are transfer points, screens, pneumatic cleaning equipment, crushers and conveyors. Frictional sparks and sparks from tramp metal are major ignition sources.[17]

The SFPE Handbook lists a high-volatility bituminous coal dust with a median particle size of 4 µm. Its minimum explosive concentration is 60 g/m³, its maximum explosion pressure 9.1 bar g and its deflagration index 59 bar·m/s.[20] Residual dust adds to the risk, because the initial "puff" of a dust explosion often disturbs settled layers and causes a secondary explosion.[17] Zalosh (2002) estimates the pressure of such a closed-volume explosion from the fraction of the mass that burns. The equation states that the fractional pressure rise equals the fraction of the total mass burned, and it can also be applied to enclosures that are only partly filled with a combustible mixture.[21]

P−P0Pm−P0=mbm0

Symbol Description Unit
P Deflagration pressure bar
P0 Initial pressure bar
Pm Maximum pressure of a closed-vessel deflagration of the dust bar
mb Mass of fuel burned (here: dust from the layer) g, or g/m² per unit floor area
m0 Mass of fuel that would fill the enclosure at the worst-case concentration g, or g/m² per unit floor area

Zalosh (2002) works an example for a coal-fired power plant. Bituminous coal dust lies on the floor at 1,000 g/m² in an enclosure with a 4 m ceiling. A primary explosion is assumed to disperse it into a worst-case cloud of 500 g/m³ in the lower part of the room.[22] A full-height cloud at that concentration would contain m0/A = 500 g/m³ × 4 m = 2,000 g/m². With Pm−P0 = 9.1 bar from the table, the pressure rise is 9.1 × (1,000/2,000) = 4.55 bar (66 psi) in an unvented room. At a typical bulk density of 500 kg/m³, the layer is only 2 mm thick.[22]

The same arithmetic shows how little dust is needed to fill such a room at the handbook's minimum explosive concentration. At 50 g/m³ over 4 m, a cloud holds 200 g/m², which corresponds to a layer about 0.4 mm thick at 500 kg/m³.[17][22] Zalosh (2002) applies the equation to an enclosure without any explosion venting and uses the closed-vessel maximum pressure from the table, so the result is an estimate for the unvented case only.[22]

The handbook therefore stresses dust control. Dust collection systems should be sized to remove coal dust as fast as it forms and located outdoors, with fans downstream of the collectors. The collectors need explosion-relief vents sized to NFPA 68.[17] Good housekeeping limits the residual dust, and vacuum cleaning removes it without raising a cloud. Vacuum tools should be non-sparking and electrically conductive, and the piping and hose permanently grounded.[17]

Sheridan (2008) adds that electrical equipment in coal-handling areas should meet the NFPA 70 criteria for Class II, Division 1 or 2, Group F locations.[8] Conveyors carry both the dust and the risk of moving burning coal through a plant; their protection is covered in Conveyor fire protection. One of the largest coal-handling fires in a 30-year US study began with an explosion in a crusher building with a serious dust condition. The fire burned several thousand feet of conveyor belt and caused $35.42 million in damage (2007 dollars) and a four-month outage; there were no fixed automatic suppression systems.[4] Coal yards and handling systems are part of wider Power station fire protection.

Limits of the guidance

The practices above are those of the US Fire Protection Handbook (2008) and the NFPA documents it cites, such as NFPA 850, NFPA 68, NFPA 70 and NFPA 600. The chapters do not state which editions they summarise.[3][17][15] NFPA 850 is a recommended practice, not a mandatory standard. The handbook also uses its units loosely. The pile of "1 million tons" is described in long tons of 1,016 kg, whereas the silo and bunker capacities are converted as short tons.[2][4] The densities and minimum explosive concentrations are ranges for typical coals, and the SFPE table gives a higher minimum explosive concentration than the handbook text.

The critical-size theory explains why large piles and long storage times are dangerous, but it needs kinetic data for the specific coal. Gray (2002) warns that extrapolating small laboratory tests to large industrial bodies requires great care, and that oxygen diffusion into the interior, multiple reactions and boundary heat losses all complicate the picture.[13] Rules of thumb such as the 4.6 m height limit for readily heating coals are practical guidance, not calculated thresholds.[15]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Dungan (2008b), p. 7-3.
  2. ↑ 2.00 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 Dungan (2008b), p. 7-4.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 Dungan (2008b), p. 7-5.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 Sheridan (2008), p. 9-183.
  5. ↑ National Research Council of Canada et al. (2005), p. 3.3-6.
  6. ↑ Van Rossum (2027), §4.2.
  7. ↑ Van Rossum (2027), §4.1.
  8. ↑ 8.0 8.1 8.2 8.3 Sheridan (2008), p. 9-182.
  9. ↑ National Research Council of Canada et al. (2005), p. 3.4-4.
  10. ↑ Iqbal and Salley (2004), p. F-56.
  11. ↑ Babrauskas (2008a), p. 6-288.
  12. ↑ Gray (2002), p. 2-211.
  13. ↑ 13.0 13.1 13.2 Gray (2002), p. 2-212.
  14. ↑ Gray (2002), p. 2-224.
  15. ↑ 15.00 15.01 15.02 15.03 15.04 15.05 15.06 15.07 15.08 15.09 15.10 15.11 15.12 15.13 Dungan (2008b), p. 7-6.
  16. ↑ Gray (2002), p. 2-225.
  17. ↑ 17.0 17.1 17.2 17.3 17.4 17.5 17.6 17.7 17.8 Dungan (2008b), p. 7-7.
  18. ↑ L. J. Moore (2008), p. 9-212.
  19. ↑ Wysocki (2008), pp. 17-7–17-8.
  20. ↑ Zalosh (2002), p. 3-404.
  21. ↑ Zalosh (2002), p. 3-408.
  22. ↑ 22.0 22.1 22.2 22.3 Zalosh (2002), p. 3-410.

References

  • Babrauskas, V. (2008a). Tables and charts. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-269–6-294). National Fire Protection Association.
  • Dungan, K. W. (2008b). Storage and handling of solid fuels. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-3–7-13). National Fire Protection Association.
  • Gray, B. (2002). Spontaneous combustion and self-heating. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-211–2-228). National Fire Protection Association; Society of Fire Protection Engineers.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Moore, L. J. (2008). Mining and mineral processing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-203–9-223). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Sheridan, D. J. (2008). Electric generating plants. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-179–9-189). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Wysocki, T. J. (2008). Carbon dioxide and application systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 17-3–17-15). National Fire Protection Association.
  • Zalosh, R. (2002). Explosion protection. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-402–3-421). National Fire Protection Association; Society of Fire Protection Engineers.