The smoke-developed index (SDI) is a relative number that expresses how much light-obscuring smoke a building material produces in the Steiner tunnel test (NFPA 255, ASTM E84).[1][2] A lamp and a photocell across the exhaust duct of the tunnel record how much light the smoke absorbs during the 10-minute test. The area under this light attenuation curve is compared with that of red oak flooring, which is set at exactly 100, and of a cement board, set at 0.[1][2] A material with an index of 450 thus gives 4.5 times the area of red oak.[1]

In the United States, NFPA 101 and NFPA 5000 (2006 editions) apply one limit of 450 to all three classes of wall and ceiling finish, A, B and C.[3] Stricter limits of 50 apply to plenum materials and air ducts.[4][5] The index is meant to protect visibility along escape routes, and the 450 limit goes back to research at Underwriters Laboratories in which smoke from the tunnel obscured illuminated exit signs.[3] It measures only the obscuration of light. It says nothing about irritancy or toxicity, and it is not directly related to the flame spread index from the same test.[3]

Definition and terminology

Hirschler describes the smoke-developed index as a tunnel result based on a concept similar to the flame spread index. The difference is that the area assigned to red oak flooring is exactly 100 by definition.[2] The smoke developed index of a specimen is determined by comparing the reduction in light caused by its smoke with the reduction caused by the smoke from red oak flooring.[1] Madrzykowski and Stroup describe the same quantity as an index representing the amount of smoke produced by the burning sample.[6]

The terminology varies between documents. Besides smoke developed index and SDI, the handbook uses smoke-developed rating, smoke development rating and smoke developed classification for the same tunnel result.[6][7][8] A table of fire tests in NUREG-1805 lists flame spread index and smoke developed as the two properties measured by ASTM E84.[9] Like the flame spread index, the smoke-developed index is a relative number without a physical unit.[10][2]

The abbreviation SDI is not unique. FM Global Test Standard 4910, used for plastics in semiconductor cleanrooms, defines a smoke development index as the product of the fire propagation index and the smoke yield of a material.[11] In that system, materials that restrict smoke development have values of 0.4 or less.[11] This index comes from tests in the fire propagation apparatus (ASTM E2058) and is a different quantity from the tunnel index, on whose scale red oak scores 100.[11][2]

Measurement in the tunnel test

The smoke measurement takes place at the downstream end of the tunnel. Air drawn through the 7.62 m (25 ft) chamber leaves through a vent pipe of 406 mm (16 in.) inside diameter, across which a light source and a photoelectric cell are mounted.[12] The photometer records the reduction in light across the exhaust caused by the smoke and particles that pass.[1] Madrzykowski and Stroup specify a white light source and a photocell that measure the light absorption in the exhaust duct.[6]

Sketch of the tunnel vent end: smoke flows from the chamber into a round duct where a lamp shines across to a photocell.
Smoke measurement in the Steiner tunnel: smoke from the test chamber passes a lamp and a photoelectric cell mounted across the 406 mm exhaust duct, which record the light attenuation during the test. Based on Hirschler (2008b), pp. 18-25–18-26 and Madrzykowski and Stroup (2008), p. 2-44.

Light attenuation by smoke follows Bouguer's law. Mulholland calls the light extinction coefficient the most widely measured smoke property. He gives the law as the ratio of transmitted to incident light intensity, which falls exponentially with the light extinction coefficient and the path length:[13]

II0=e−KL=10−DL,D=K2.3

The quantity D is the optical density per metre.[13] The product DL is the optical density over the whole beam, a dimensionless number that test standards such as NFPA 262 use as a limit.[13][14] The extinction coefficient equals the mass concentration of smoke times a specific extinction coefficient, measured at 7.6 m²/g for flaming wood and plastics (Seader and Einhorn, as cited in Mulholland, 2002).[13]

The index itself compares areas under the attenuation curves over time. Hirschler explains that an index of 450 means a curve with 4.5 times the area of the red oak curve, both measured relative to the cement board.[1] This description can be written as a simple ratio:

SDI=100AsARO

Symbol Description Unit
SDI smoke-developed index – (non-dimensional)
As area under the light attenuation curve of the specimen over the test, relative to cement board any (only the ratio is used)
ARO area under the light attenuation curve of red oak flooring, relative to cement board any (only the ratio is used)
I,I0 transmitted and incident light intensity W/m² (any consistent unit)
K light extinction coefficient m⁻¹
D optical density per metre m⁻¹
L path length of the light beam through the smoke m

The ratio is a simplified reading of the handbook description; the test standard defines the procedure in detail. Because only areas are compared, the units of the attenuation measurement cancel. Hirschler adds that, in simple terms, an index of 450 means about 4.5 times the smoke that red oak flooring produces during a 10-minute test.[3]

Schematic chart of light attenuation against time: a small shaded area for red oak and an area 4.5 times larger for a product with index 450.
Principle of the smoke-developed index: the area under the light attenuation curve over the 10-minute test is compared with that of red oak flooring (100); a product with an index of 450 has 4.5 times the red oak area. Schematic, not measured data. Based on Hirschler (2008b), pp. 18-26–18-27.

Worked example

A sprayed polyurethane foam, 51 mm thick and flame retardant, reached a smoke developed classification of 935 in a series of tests by Underwriters Laboratories.[8] From the ratio above, its light attenuation area was 935/100 = 9.35 times that of red oak. That is 935/450 = 2.08 times the limit for Classes A, B and C, although its flame spread classification was 18, well within Class A.[8][3] A 2 in. (51 mm) extruded polystyrene board in the same work reached 785, or 7.85 times red oak, with a flame spread classification of only 3.[8]

The NFPA 262 limits for plenum cables show how optical density translates into transmitted light. A peak optical density of 0.5 over the beam means that I/I0=10−0.5 = 0.316, so 31.6 percent of the light still reaches the photocell. An average optical density of 0.15 corresponds to 70.8 percent.[14][13]

The limit of 450

In the United States, the classification of wall and ceiling finishes in NFPA 101 and NFPA 5000 (2006 editions), as described by Hirschler (2008b), rests mainly on the flame spread index. A single smoke-developed limit of 450 is common to all classes.[3] The tables of the Life Safety Code (2006) state this limit for new applications.[15] The smoke index assesses product behaviour in terms of obscured exit paths and loss of visibility.[3] Smoke reduces visibility through the soot and other particles accumulated in a given volume, so the smoke level depends both on time and on the rate of smoke production.[3]

The same limit applies everywhere in a building, unlike the flame spread classes. Flame spread mainly threatens people close to the fire, but smoke affects visibility both near the fire and in remote areas.[3] Large buildings can be filled with smoke quickly. An upper limit has therefore been set that applies to interior finishes regardless of where they are installed.[3]

The value of 450 comes from research by Underwriters Laboratories, reported in its Bulletin of Research No. 56 (1965).[3][16] Products were burned in the tunnel and the smoke was discharged into a room of 142 m³ (5,000 ft³) equipped with illuminated exit signs.[3] The time until the signs were obscured was compared with the smoke-developed index of each material. Materials above 325 showed "good" to "marginal" visibility in a few cases, while others produced "marginal" visibility to "obscuration" within 6 minutes.[3] The limit of 450 has long been thought to be reasonable. It takes into account both the time needed to produce the smoke and its effect on vision distance.[3]

The use of illuminated signs in that research matters, because visibility depends on the type of sign. Mulholland reports Jin's finding that light-emitting signs remain visible two to four times farther than light-reflecting signs in the same smoke.[17] Van Rossum gives a rule of thumb for the visibility distance: 2.5 divided by the optical density for a luminous object, and 1 divided by the optical density for an object that only reflects light.[18] He stresses that visibility also depends on contrast, light scattering and irritating smoke components, so the rule is only approximate.[18]

Other limits based on the index

In the United States, several standards use the index with lower limits than 450. Plenum materials must have a smoke-developed index of 50 or less, with a flame spread index of 25 or less, as summarised by Hirschler (2008a).[4] Under the UL standards for air ducts and connectors, as described by Webb (2008), Class 1 ducts may have a smoke developed rating of at most 50. Class 2 ducts may have 50 on the inside surface and 100 on the outside surface.[5] Plastic ducts for corrosive vapours need at most 50 to NFPA 255, as described by Lataille (2008).[19] The original ceiling tiles of the World Trade Center towers had a smoke developed index under 50 according to their manufacturer (Fritz and Hough 2002, as cited in Gann, Hamins, et al., 2005).[20]

For elevator cars, the limit matches that for exits. ASME A17.1/CSA B44, as described by Donoghue (2008), allows a smoke development rating of 0 to 450 for materials exposed in the car. That value equals the NFPA 101 requirement for an exit passageway in a fire-resistant building.[7] Donoghue notes that smoke may matter more than flame spread in a car, because passengers in a confined box may not be able to escape quickly. Canadian fire fighter elevators under the National Building Code of Canada need 0 to 100 for walls and ceilings and 0 to 300 for floors.[7]

The 450 limit also appears in other building rules. Under the model building codes described by Benedetti and Colonna (2008), some foam plastics may be used without a thermal barrier, for example in masonry cavities or under slabs. They must then reach 450 or less, together with a flame spread rating of 75 or less.[21] For dwellings, Sumathipala reports the same 450 limit in the 2006 editions of NFPA 5000 and NFPA 101.[22] A definition of fire-retardant coatings by Nolan limits their smoke developed rating to 200.[23]

Scale from 0 to 500 with limit markers: 50 for plenums and ducts, 100 for Canadian fire fighter lifts, 200 for coatings, 450 for interior finish.
Main smoke-developed limits in United States and Canadian documents as described in the 2008 Fire Protection Handbook and NUREG-1805. Based on Hirschler (2008a), p. 6-44; Hirschler (2008b), p. 18-27; Webb (2008), p. 10-72; Donoghue (2008), p. 10-63; Iqbal and Salley (2004), p. F-28.

Some products are exempt from any smoke limit. Interior trim covering no more than 10 percent of the wall or ceiling area must meet Class C for flame spread, but without a smoke-developed limit. The same applies to foam plastic trim of Class B and to small areas of electrical raceways.[24] Floor coverings are not generally regulated on smoke in the codes. They normally become involved only when a fire is already large and the smoke production very high.[25]

Typical values

Published values range from almost zero to well above 1000. In the Underwriters Laboratories study behind the limit, one material had a flame spread index of 490 and a smoke-developed index of 57. Another had 44 and 1387.[3] The table collects other tunnel results from the 2008 handbook.

Smoke-developed index (or smoke developed classification) of selected products in the Steiner tunnel test[2][26][27][8]
Product Smoke-developed index Flame spread index Source
Red oak flooring (reference) 100 about 100 Hirschler (2008a), p. 6-43
Cement board (reference) 0 0 Hirschler (2008a), p. 6-43
Untreated Douglas fir 100 100 Shaw (2008), p. 6-135
Douglas fir with three listed fire-retardant coatings 5 to 40 10 to 60 Shaw (2008), p. 6-135
Pressure-impregnated lumber, plywood and particleboard 25 or less 25 or less Shaw (2008), p. 6-134
Glass fibre blanket, 89 mm, unfaced 3 18 Benedetti and Colonna (2008), p. 6-226
Wood particleboard, 12.7 mm, flame retardant 37 18 Benedetti and Colonna (2008), p. 6-226
Extruded polystyrene board, 51 mm, flame retardant 785 3 Benedetti and Colonna (2008), p. 6-226
Polyurethane spray foam, 51 mm, flame retardant 935 18 Benedetti and Colonna (2008), p. 6-226

The values show that low flame spread and low smoke do not go together. The four materials with a flame spread classification of 18 produced smoke developed classifications of 3, 4, 37 and 935.[8] Fire-retardant coatings on Douglas fir reduced the smoke developed value from 100 to between 5 and 40, depending on the product.[26] Pressure-impregnated wood products in Shaw's table reach 25 or less for both indices.[27]

Paired bars for six products: flame spread index and smoke-developed index differ widely, from FSI 490 with SDI 57 to FSI 18 with SDI 935.
Flame spread index and smoke-developed index of the same products in the Steiner tunnel: low flame spread does not mean low smoke, and the reverse. Based on Hirschler (2008b), p. 18-27 and Benedetti and Colonna (2008), p. 6-226.

Relation to flame spread and heat release

There is no direct relationship between the flame spread index and the smoke-developed index.[3] The two indices come from different measurements in the same test, and a product can score well on one and badly on the other. Heat release and mass loss, however, control the amount of smoke released into a given volume, and thus visibility.[28] Low heat release does not always mean low smoke, either. In five series of room-corner tests, two in Europe and three in the United States, 10 of 84 materials gave low heat release but very high smoke release.[29]

Large-scale tests therefore include a smoke criterion. The 2006 editions of the United States codes require a total smoke release of no more than 1000 m² for new installations tested to the NFPA 286 room-corner test.[30] Hirschler describes this value as roughly equivalent to the smoke-developed limit of 450 in the tunnel.[29] The codes admit room-corner results on the premise that materials that do not cause flashover or high smoke release there have a tunnel index below 450.[30]

In the European classification of construction products, smoke is a separate additional class. Class s1 requires a smoke growth rate of at most 30 m²/s² and a total smoke production over 600 seconds of at most 50 m² in the single burning item test. Class s2 allows 180 m²/s² and 200 m², and s3 covers all other products.[31] These criteria are expressed in physical units, unlike the tunnel index.[31]

A third approach is the smoke density chamber, ASTM E662. It measures the specific optical density of smoke from a specimen in a closed chamber of 0.5 m³ under a radiant heat flux of 25 kW/m².[14] This is a static test, while the tunnel and the cone calorimeter are dynamic tests with air and smoke flowing through them.[14] The chamber is widely used for trains and aircraft but not normally for interior finish in building codes. Its closed volume can become oxygen deficient, and soot deposits can affect the measurement.[29][32]

Limitations and misconceptions

The index measures obscuration of light and nothing else. Hirschler points out that smoke may also act as an irritant, which further reduces visibility, and may have a debilitating effect on people trying to escape.[3] These irritant and physiological effects are not evaluated by the 450 limit.[3] A low index is therefore not evidence of low toxicity.

The measurement itself has limits. Bouguer's law is strictly valid only for monochromatic light. Foster predicted a deviation of 22 percent for a polychromatic light source with wood smoke over a range of concentrations (as cited in Mulholland, 2002).[13] The tunnel photometer uses white light, so Bouguer's law applies to its readings only approximately.[6][13] The index also inherits the limits of the tunnel test. Adhesives and mounting can significantly change both indices, and melting or foamed products may behave very differently in a real room.[1][30]

The index is not an engineering quantity. Like the flame spread index, it gives no result in engineering units.[10] Fire hazard calculations use quantities such as the smoke yield, the mass of smoke per unit mass of material burned. Tests with an exhaust hood or duct provide it from the optical density, the exhaust flow and the mass loss.[6] Van Rossum then calculates the optical density in a room from the smoke concentration and an extinction coefficient.[33] Hirschler considers present fire testing of interior finish probably adequate to eliminate the poorest performers, both for flame spread and for smoke release.[34]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 1.4 1.5 1.6 Hirschler (2008b), p. 18-26.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 Hirschler (2008a), p. 6-43.
  3. ↑ 3.00 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 Hirschler (2008b), p. 18-27.
  4. ↑ 4.0 4.1 Hirschler (2008a), p. 6-44.
  5. ↑ 5.0 5.1 Webb (2008), p. 10-72.
  6. ↑ 6.0 6.1 6.2 6.3 6.4 Madrzykowski and Stroup (2008), p. 2-44.
  7. ↑ 7.0 7.1 7.2 Donoghue (2008), p. 10-63.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 8.5 Benedetti and Colonna (2008), p. 6-226.
  9. ↑ Iqbal and Salley (2004), p. C-12.
  10. ↑ 10.0 10.1 Hirschler (2008a), p. 6-42.
  11. ↑ 11.0 11.1 11.2 DeGiorgio and Peterkin (2008), p. 9-128.
  12. ↑ Hirschler (2008b), p. 18-25.
  13. ↑ 13.0 13.1 13.2 13.3 13.4 13.5 13.6 Mulholland (2002), p. 2-263.
  14. ↑ 14.0 14.1 14.2 14.3 Hirschler (2008a), p. 6-45.
  15. ↑ Hirschler (2008b), p. 18-28.
  16. ↑ Hirschler (2008b), p. 18-40.
  17. ↑ Mulholland (2002), p. 2-265.
  18. ↑ 18.0 18.1 Van Rossum (2027), §6.5.
  19. ↑ Lataille (2008), p. 8-7.
  20. ↑ Gann, Hamins, et al. (2005), p. 45.
  21. ↑ Benedetti and Colonna (2008), p. 6-229.
  22. ↑ Sumathipala (2008), p. 19-62.
  23. ↑ Nolan (2000), as cited in Iqbal and Salley (2004), p. F-28.
  24. ↑ Hirschler (2008b), p. 18-36.
  25. ↑ Hirschler (2008b), p. 18-35.
  26. ↑ 26.0 26.1 Shaw (2008), p. 6-135.
  27. ↑ 27.0 27.1 Shaw (2008), p. 6-134.
  28. ↑ Hirschler (2008b), p. 18-23.
  29. ↑ 29.0 29.1 29.2 Hirschler (2008b), p. 18-32.
  30. ↑ 30.0 30.1 30.2 Hirschler (2008b), p. 18-31.
  31. ↑ 31.0 31.1 Hirschler (2008a), p. 6-52.
  32. ↑ Hirschler (2008b), p. 18-33.
  33. ↑ Van Rossum (2027), §6.4.
  34. ↑ Hirschler (2008b), p. 18-39.

References

  • Benedetti, R. P., & Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-209–6-231). National Fire Protection Association.
  • DeGiorgio, V., & Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-119–9-129). National Fire Protection Association.
  • Donoghue, E. A. (2008). Building transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-57–10-68). National Fire Protection Association.
  • Gann, R. G., Hamins, A., McGrattan, K. B., Mulholland, G. W., Nelson, H. E., Ohlemiller, T. J., Pitts, W. M., & Prasad, K. R. (2005). Reconstruction of the fires in the World Trade Center towers (NIST NCSTAR 1-5). National Institute of Standards and Technology.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 18-23–18-42). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Mulholland, G. W. (2002). Smoke production and properties. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 2-258–2-268). National Fire Protection Association; Society of Fire Protection Engineers.
  • Shaw, J. R. (2008). Fire-Retardant and flame-resistant treatment of cellulosic materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-129–6-139). National Fire Protection Association.
  • Sumathipala, K. (2008). Structural fire safety in one- and two-family dwellings. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 19-59–19-64). National Fire Protection Association.
  • Van Rossum, E. (2027). Introduction to Fire Safety Engineering. Fire Safety Academy.
  • Webb, W. A. (2008). Air-Conditioning and ventilating systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-69–10-76). National Fire Protection Association.