Summary
Theoretical minimum and minimum design carbon dioxide concentrations for inerting ethylene oxide and other fuels; the design value is 20 percent above the theoretical value but at least 34 percent. Based on Wysocki (2008), pp. 17-5–17-6.
Original illustration for Ethylene oxide.
- Source basis: Wysocki (2008), pp. 17-5–17-6, Table 17.1.1 (Bureau of Mines data) (redraw, do not copy)
- Alt text: Bar chart: carbon dioxide theoretical and design concentrations; ethylene oxide 44 and 53 percent, methane 25 and 34 percent, hydrogen 62 and 75 percent.