Contents
Fse-silane-v3.svg (SVG file, nominally 1,360 × 760 pixels, file size: 6 KB)
Summary
Main features of a ventilated silane gas cabinet: a restricted flow orifice limits the leak rate, continuous exhaust dilutes and removes the gas to treatment, and the exhaust is monitored. Based on DeGiorgio and Peterkin (2008), pp. 9-126–9-127 and Anderson (2008a), p. 9-165.
Original illustration for Silane.
- Source basis: DeGiorgio and Peterkin (2008), p. 9-126 (pyrophoric gases outside the plant, welded stainless steel tubing, exhaust gas conditioning, continuous monitoring), p. 9-127 (gas cabinet ventilation guidance of NFPA 318, RFO table); Anderson (2008a), p. 9-165 (ventilated gas cabinets with sprinkler protection inside for pyrophoric gases)
- Alt text: Cross-section of a gas cabinet with a silane cylinder, restricted flow orifice, exhaust duct to treatment, gas detector and internal sprinkler.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.