  1. 1Summary
  2. 2Licensing

Fse-fire-retardant-treated-wood-v3.svg (SVG file, nominally 1,190 × 735 pixels, file size: 21 KB)

Summary

Estimated time to ignition of 12.7 mm untreated and fire-retardant plywood against incident heat flux, from the correlation of Mikkola and Wichman. Based on Iqbal and Salley (2004), pp. 6-8 and 6-10–6-11.

Original illustration for Fire-retardant-treated wood.

  • Source basis: Iqbal and Salley (2004), p. 6-8 (correlation from the SFPE engineering guide) and pp. 6-10–6-11 (Table 6-5 properties)
  • Alt text: Line chart of time to ignition against heat flux; untreated plywood curve near 30 s at 60 kW/m², treated curve near 840 s, rising steeply towards 44 kW/m².