Estimated time to ignition of 12.7 mm untreated and fire-retardant plywood against incident heat flux, from the correlation of Mikkola and Wichman. Based on Iqbal and Salley (2004), pp. 6-8 and 6-10–6-11.
Original illustration for Fire-retardant-treated wood.
- Source basis: Iqbal and Salley (2004), p. 6-8 (correlation from the SFPE engineering guide) and pp. 6-10–6-11 (Table 6-5 properties)
- Alt text: Line chart of time to ignition against heat flux; untreated plywood curve near 30 s at 60 kW/m², treated curve near 840 s, rising steeply towards 44 kW/m².