Revision as of 22:38, 7 November 2026 by Mark (talk | contribs) (FSE wiki: fact-check: hedges restored, NFPA 55 MAQ liquefied/nonliquefied, Table 9.9.1 unit reading flagged, FPI example 78 kW/m, Tewarson pages, sprinkler example context (written by Claude Opus 5.5))
Contents
  1. 1Manufacturing processes and hazardous materials
  2. 2Cleanroom design and air handling
  3. 3Fire and explosion hazards
    1. 3.1Flammable liquids
    2. 3.2Flammable, pyrophoric and toxic gases
    3. 3.3Combustible tools, wet benches and wafer carriers
  4. 4Silane gas cabinet ventilation
  5. 5Codes, guidelines and material testing
  6. 6Fire protection measures
  7. 7Limits and uncertainty
  8. 8See also
  9. 9Notes
  10. 10References

A semiconductor fabrication facility, often shortened to fab,[1] is a plant in which integrated circuits, or chips, are built up layer by layer on thin wafers of silicon or another semiconductor material inside a cleanroom.[2][3] Finished chips generally present no unique hazard, but the manufacturing process uses acids, alkalis, flammable liquids, flammable gases, pyrophoric gases and toxic gases.[2] The 20th edition of the NFPA Fire Protection Handbook (2008) puts the cost of building and equipping a large facility at 2 to 3 billion US dollars.[2] Wafers in process are very susceptible to fire and smoke damage, and business interruption adds to the loss.[2] In the United States, NFPA 318, Standard for the Protection of Semiconductor Fabrication Facilities, covers construction, sprinklers, detection, ventilation, tools and chemicals; the handbook describes its 2006 edition.[4] The main protection themes are tools of noncombustible or nonpropagating materials, very early smoke detection, gas detection and the safe handling of pyrophoric silane.

Manufacturing processes and hazardous materials

Integrated circuits are made from silicon, a semiconductor whose electrical conductivity can be changed by adding minute quantities of chemicals called dopants.[2] Other semiconductor materials include gallium arsenide, germanium and indium arsenide. Raw wafers are generally bought from outside suppliers; they are sliced from crystal ingots to a thickness of 0.36 to 0.76 mm, and 300 mm wafers were widely used by 2008.[3] Inside the fab, each wafer passes through repeated steps of applying photoresist, photomasking, developing, etching, doping and deposition until the circuit is complete.[5] Forty or more layers of circuit patterns may be combined on a single chip.[3]

Each step brings its own chemicals. Photoresist and its developer are the largest volumes of solvent in the fabrication area.[5] Negative photoresist is a light-sensitive polymer in a flammable organic solvent such as xylene or toluene. It is developed with xylene and washed with butyl acetate or isopropyl alcohol, whereas positive resist uses alkaline developers and deionised water.[6]

Etching removes material in the pattern left by the resist. Wet etching with acid mixtures predominates and is normally done in plastic wet benches with plastic exhaust ductwork.[6] Dry etching uses reactive gases containing chlorine or fluorine in a highly energised vacuum chamber. Doping by diffusion takes place at 900 to 1300 °C, and chemical vapour deposition (CVD) builds thin films from reacting gases.[6] The gases used include pyrophoric silane as a source of silicon and the highly toxic arsine, phosphine and diborane.[7][8]

Fabs for 300 mm wafers, more than 40 of them by 2008, are highly automated.[1] A front-opening unified pod (FOUP) carries 24 wafers and weighs 8 kg, so overhead hoists and guided vehicles move it rather than people. FOUPs wait in stockers, which are self-contained vertical storage units inside the cleanroom. Most FOUPs are made of combustible plastics, and large-scale tests by FM Global confirmed that they are a significant fire hazard inside a stocker.[1] Their tools are 1.0 to 1.5 times larger than 200 mm tools, and etch tools draw more than 250 A at 208 V. Unless noncombustible or fire-safe plastics are used, larger tools add fuel; the higher power adds ignition energy, and fewer operators mean later discovery of a fire.[4]

Cleanroom design and air handling

A cleanroom holds airborne particles below a stated limit, because a single microscopic dust particle can ruin a chip.[2] A Class 100,000 cleanroom holds fewer than 100,000 particles larger than 0.5 µm per cubic foot (0.028 m³), about 3.5 million per cubic metre.[9] The most advanced chips need Class 1 design: fewer than one particle larger than 0.12 µm per cubic foot. For comparison, normal urban air contains about 5,000,000 particles per cubic foot and fire smoke can contain 1 trillion.[3] Wafer fabrication itself takes place in Class 1 to Class 10,000 cleanrooms.[10]

Tewarson (2002) describes a sealed room supplied with clean air, built of noncontaminating polymers and protected against contamination from outside, from operators and from accidental fires.[11] Nearly all semiconductor cleanrooms use laminar flow, in which air moves in unidirectional layers at 0.2 to 0.5 m/s (40 to 100 ft/min).[12] Up to 10 air changes per minute may occur, with typical airflows of 6 to 15 m³/min per square metre of floor (20 to 50 cfm/ft²).[12]

Air returns through sidewall vents, a perforated raised floor 0.3 to 1.2 m high, or openings into a basement plenum.[12] Between 80 and 95 percent of the supply is recirculated air. A slight positive pressure of about 40 Pa (0.15 in. water) makes leakage flow outwards.[12] High-efficiency particulate air (HEPA) filters must remove 99.97 percent of 0.3 µm particles; in the United States they are tested to UL 586.[13]

In a cleanroom, much of the fire loss can come from contamination. A glossary in NUREG-1805, a US Nuclear Regulatory Commission report, notes that smoke and combustion gases may cause more property damage than the fire itself in some locations, naming high-technology clean rooms as an example.[14] Harmful chemicals from the smoke can be deposited on the products and make them unsuitable for use or salvage.[14] Materials that meet the FM 4910 criteria produce less smoke and fewer corrosive products when they burn, which reduces such nonthermal damage.[8]

Fire and explosion hazards

Most fab hazards, such as plating, crystal growing and flammable liquids and gases, also occur in other industries with established controls.[10] Less common are pyrophoric gases, toxic materials, radio-frequency fields, ionising radiation and the handling that chemical purity demands. For fire protection, three groups stand out: flammable liquids, flammable and pyrophoric gases, and the combustible plastics of tools and wafer carriers.

Flammable liquids

Most flammable liquids in chip fabrication are alcohols and alcohol-based mixtures.[12] Storage and handling generally follow NFPA 30, and containers travel to the cleanroom on purpose-built carts that hold them upright and contain leaks. Liquids not in use belong in listed storage cabinets, and piped supply uses closed, dual-contained bulk dispensing.[12] The flash point is the temperature at which a liquid gives off enough vapour for ignition.[15] The International Fire Engineering Guidelines list flash points of 13 °C for ethanol and 4 °C for toluene.[16]

Flammable, pyrophoric and toxic gases

A pyrophoric gas is a flammable gas that ignites spontaneously in air, without an ignition source.[15] Examples are silane and phosphine, and such gases are most likely to be found in semiconductor manufacturing.[15] The International Fire Engineering Guidelines give silane flammability limits of 1.0 and 100 percent by volume and an autoignition temperature of −100 °C.[16] In fabs these gases may be used pure or mixed with a carrier gas such as hydrogen or nitrogen.[12]

Released silane may ignite at once with a visible flame, or escape with no ignition or delayed ignition, possibly ending in a detonation.[7] In a confined space such as a gas cabinet, silane has been known to detonate. In unconfined areas such as outdoors, pyrophoric gases usually ignite on release and then burn like other flammable gases. Their burning behaviour is not fully understood, mainly because engineering controls have prevented most uncontrolled releases.[17]

Pyrophoric and toxic gases should be placed outside the plant and piped to the cleanroom in welded stainless steel tubing.[12] Tools using high concentrations of pyrophoric gases need exhaust gas conditioning and continuous exhaust monitoring.[12] Compressed Gas Association release studies led to publication P32-2000, now G-13, whose data have been used to establish minimum separation distances for silane systems.[7] The NFPA 55 (2005) limits in the handbook allow no pyrophoric gas in an unsprinklered control area. In a sprinklered area with gas cabinets, the limit is 2.8 m³ (100 ft³) of nonliquefied or 3.6 kg (8 lb) of liquefied gas.[18] NFPA 55 also keeps pyrophoric cylinders 6.1 m (20 ft) from flammable, oxidising and toxic gases, unless separated by a noncombustible barrier at least 1.5 m high with a half-hour fire resistance rating.[19]

Arsine, phosphine and diborane are highly toxic, so they are monitored continuously and treated in the tool exhaust.[8] A fixed gas detection system is needed wherever permanent gas hazards exist, and fabs are a typical application.[20] Smoke detector spacing rules from NFPA 72 do not apply, because a gas leak has no fire plume to carry gas to the ceiling.[20] Readings are usually given as a percentage of the lower flammable limit (LFL).[21]

Combustible tools, wet benches and wafer carriers

Workstations, wet benches and other equipment are designed to release few particles and to resist process chemicals.[7] The hazard of a wet bench lies in the confined spaces beneath it, vats of flammable liquid on its polypropylene surface and its collector hoods.[22] Tools inside large minienvironments can contain thousands of pounds (roughly a tonne or more) of plastics, which in most cases are shielded from the building sprinklers.[4] Until about 2000 the industry often judged these tools by the UL 94 V-0 rating, developed for small plastic appliances and never intended for them.[4] The UL 94 vertical test exposes a strip 125 mm long and 13 mm wide to a 50 W flame for 10 seconds.[23]

Silane gas cabinet ventilation

NFPA 318 contains performance-based guidance on silane gas cabinet ventilation rates, based on FM Global research tests.[7] The handbook reproduces two NFPA 318 (2006) data sets. One gives the silane flow through restricted flow orifices (RFOs) of 0.25 to 0.51 mm at 3.5 to 103.4 bar, for a source temperature of 25 °C and a discharge coefficient of 0.8. The other gives the average concentration in a ventilated enclosure. For a 0.25 mm orifice at 103.4 bar (1500 psi) the table gives 1.18 and 2.50; the units are not printed, but the pairs match litres per second and cubic feet per minute. The flow through 0.36 mm and 0.25 mm orifices is 49 and 25 percent of the flow through a 0.51 mm orifice.[7]

The concentration chart can be reproduced with a simple volume balance. If the leak mixes completely with the exhaust air, its volume fraction is the leak flow divided by the total flow. Because the leak is small, the total is close to the exhaust flow:

C=V˙gV˙g+V˙e≈V˙gV˙e

Symbol Description Unit
C Average volume fraction of silane in the enclosure exhaust – (or vol%)
V˙g Silane flow through the restricted flow orifice L/s
V˙e Ventilation (exhaust) flow through the enclosure L/s

Worked example. Reading the table value as litres per second, a 0.25 mm orifice at a source pressure of 103.4 bar releases 1.18 L/s of silane. At an exhaust flow of 425 L/s the balance gives 0.28 percent, close to the roughly 0.26 percent read from the NFPA 318 chart; at 708 L/s it gives 0.17 against about 0.18 percent.[7] Silane has a lower flammability limit of 1.0 percent by volume.[16] The handbook uses 25 percent of the LFL as a ventilation target where flammable vapours are released, which here means 0.25 percent.[24] Reaching it needs 1.18/0.0025 = 472 L/s, or about 1,900 L/s with a 0.51 mm orifice.

Orifice size and source pressure thus govern the exhaust flow needed. The 25 percent target is only an illustration, since the handbook does not state the criterion NFPA 318 applies to gas cabinets.[7] A pyrophoric gas may also ignite before it mixes, so the flammability limit is not the only design question.

Codes, guidelines and material testing

In the United States, NFPA 318 was first published in 1992 and was in its 2006 edition when the handbook was written.[4] It applies to any semiconductor facility with a cleanroom or clean zone. It covers construction including seismic protection, sprinkler and detection design, ventilation and local exhaust, and equipment interlocks and electrical design. Chemical storage and handling is also covered, with particular attention to gas cylinders and bulk silane systems.[4] NFPA 5000 requires buildings with cleanrooms in such facilities to be built to NFPA 318.[4]

The handbook calls the new rule for tools possibly the most significant change to the standard: tools should be of noncombustible construction.[7] Three exceptions apply: small parts, listed nonfire-propagating materials, and other controls such as sprinklers or detection and suppression systems.[25] The guidelines of Semiconductor Equipment and Materials International (SEMI) follow a similar order. SEMI S14 asks first to eliminate the hazard, then to use nonpropagating materials, and only then to add detection, suppression or power shutdown.[26] SEMI S2-0703A calls for equipment fire risk to be assessed and reported, with suppression only where the assessment shows a need.[10]

Nonpropagating materials are identified with FM Global Test Standard 4910, whose apparatus is the fire propagation apparatus of ASTM E2058 and whose method is NFPA 287.[8] It uses small-scale ignition, propagation and combustion tests, with a large-scale validation where needed. That check is the parallel panel test: two panels 2.4 m high facing each other across a 60 kW sand burner for 20 minutes.[23] Underwriters Laboratories developed UL 2360, based on the cone calorimeter, as an alternative route for tool plastics.[8][27]

The fire propagation index (FPI) combines resistance to ignition with the heat released during upward flame spread. The upward test uses air enriched to an oxygen mass fraction of 0.40 to simulate the flame radiation of large fires.[28] The index is defined as:

FPI=1000(0.42Q˙'ch)1/3TRP=750(Q˙'ch)1/3TRP

Symbol Description Unit
FPI Fire propagation index (m/s1/2)/(kW/m)2/3
Q˙'ch Chemical heat release rate per unit sample width during upward fire propagation kW/m
TRP Thermal response parameter, which relates the time to ignition to the net heat flux kW·s1/2/m²

Materials with an FPI of 6 or less are nonpropagating, and their smoke development index (SDI), the FPI times the smoke yield, must not exceed 0.4.[8] The handbook defines three classes of tested plastics. Class 1 adds a flame spread of no more than 1.2 m (4 ft) in the parallel panel test.[8]

Worked example. Tewarson (2002) takes a sheet with a TRP of 95 kW·s1/2/m² releasing 50 kW over a width of 0.3 m, or 167 kW/m. The FPI is about 43, an accelerating Group 3 material.[29] To keep the FPI at 6 or less, this TRP allows only about 0.44 kW/m, whereas a cable with a TRP of 535 kW·s1/2/m² from another example allows about 78 kW/m.[29] Several highly halogenated thermoplastics and high-temperature thermosets meet the cleanroom criteria, and polyethylene, polypropylene and PVC can be modified to do so.[30]

Fire protection measures

The handbook recommends fire-resistant buildings, with cleanrooms cut off from other areas by construction rated for at least 1 hour.[10] Because of the high values, further compartmentation is highly desirable. Recirculating air should be able to shut down in a fire or spill, while toxic process exhaust keeps running and helps remove smoke. Sprinklers inside fume exhaust ducts need care, because their discharge can significantly reduce the exhaust flow.[10]

According to the handbook, cleanrooms must be equipped with a fully automatic, fast-response sprinkler system.[10] NFPA 13, as summarised in the handbook, defines fast-response sprinklers by a response time index (RTI) of 50 m1/2·s1/2 or less, against 80 or more for standard response.[31] The ceilings of 300 mm fabs, at least 4.5 m and up to 7 m, lengthen sprinkler response, so the fire is larger when sprinklers operate.[32] The handbook gives the minimum heat release rate that can operate a sprinkler in the ceiling jet for r/hceil > 0.18:[31]

Q˙min=0.08(Top−T∞)3/2hceil3/2r

Symbol Description Unit
Q˙min Total heat release rate needed to operate the sprinkler (steady fire) kW
Top Activation temperature of the sprinkler °C
T∞ Initial ambient temperature °C
hceil Distance from the fuel surface to the ceiling m
r Radial distance from the fire axis to the sprinkler m

Worked example. A handbook example places a fire centrally between four sprinklers on a 4.5 m grid (r = 3.18 m), rated 74 °C, in air at 20 °C. For its 4.0 m ceiling the handbook obtains 810 kW.[33] With the fuel at floor level, the same equation gives about 970 kW for a 4.5 m ceiling and 1,900 kW for a 7.0 m ceiling (r/hceil 0.71 and 0.45). The higher ceiling needs a fire almost twice as large before a sprinkler can operate. The equation only shows whether the ceiling jet can reach the activation temperature; the sensing element then still needs time to heat up.[31]

Cleanrooms use very sensitive smoke detection. Spot-type detectors with a laser light source can be up to 100 times more sensitive than LED units and are intended for uses such as cleanrooms.[34] Air sampling smoke detectors draw air through sampling pipes to a detector with an intense light source and reach very high sensitivity. Transport time limits the pipe length, smoke is diluted in proportion to the number of ports, and the flow at a single port is usually not supervised.[34] Wafer stockers can be protected by sprinklers, by high-sensitivity detection with gaseous suppression, or by nonfire-propagating FOUPs tested to FM 4911.[1]

Portable extinguishers follow an extra-hazard schedule, and carbon dioxide (CO2) units are the most common type in cleanrooms.[10] Dry chemical is not recommended: the powder contaminates wafers beyond salvage, and cleaning equipment and replacing HEPA filters is expensive. Wet benches have traditionally been protected by carbon dioxide systems.[22] FM Global has approved water mist systems for them, with open nozzles, optical detectors and corrosion-resistant piping.[22] Selected equipment may also receive fine water spray or gaseous agents such as CO2 or FM-200.[10]

Limits and uncertainty

The handbook describes US practice around 2008, with NFPA 318 (2006), NFPA 55 (2005) and SEMI S14-0704.[26][18] Later editions may differ, and other countries apply their own rules. Pyrophoric gas burning is not fully understood, and silane separation distances rest largely on release studies.[17] The volume balance used above assumes complete mixing of the leak with the exhaust air.

The ceiling-jet equations hold for horizontal, unobstructed ceilings without a smoke layer; a layer raises temperatures.[35] Predicted operating times can be badly wrong when the gas temperature barely exceeds the activation temperature.[33] The FPI and SDI criteria come from bench-scale tests, although materials with a low FPI are likely to perform well in the parallel panel test.[36] Health hazards such as ionising, laser, radio-frequency and ultraviolet radiation also occur in fabs but fall outside the handbook's scope.[8]

See also

Notes

  1. ↑ 1.0 1.1 1.2 1.3 DeGiorgio and Peterkin (2008), p. 9-123.
  2. ↑ 2.0 2.1 2.2 2.3 2.4 2.5 DeGiorgio and Peterkin (2008), p. 9-119.
  3. ↑ 3.0 3.1 3.2 3.3 DeGiorgio and Peterkin (2008), p. 9-120.
  4. ↑ 4.0 4.1 4.2 4.3 4.4 4.5 4.6 DeGiorgio and Peterkin (2008), p. 9-124.
  5. ↑ 5.0 5.1 DeGiorgio and Peterkin (2008), p. 9-121.
  6. ↑ 6.0 6.1 6.2 DeGiorgio and Peterkin (2008), p. 9-122.
  7. ↑ 7.0 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 DeGiorgio and Peterkin (2008), p. 9-127.
  8. ↑ 8.0 8.1 8.2 8.3 8.4 8.5 8.6 8.7 DeGiorgio and Peterkin (2008), p. 9-128.
  9. ↑ DeGiorgio and Peterkin (2008), pp. 9-119–9-120.
  10. ↑ 10.0 10.1 10.2 10.3 10.4 10.5 10.6 10.7 DeGiorgio and Peterkin (2008), p. 9-125.
  11. ↑ Tewarson (2002), p. 3-94.
  12. ↑ 12.0 12.1 12.2 12.3 12.4 12.5 12.6 12.7 12.8 DeGiorgio and Peterkin (2008), p. 9-126.
  13. ↑ Webb (2008), p. 10-72.
  14. ↑ 14.0 14.1 Nolan (2000), as cited in Iqbal and Salley (2004), p. F-51.
  15. ↑ 15.0 15.1 15.2 Lemoff (2008), p. 6-166.
  16. ↑ 16.0 16.1 16.2 National Research Council of Canada et al. (2005), p. 3.3-3.
  17. ↑ 17.0 17.1 DeGiorgio and Peterkin (2008), pp. 9-126–9-127.
  18. ↑ 18.0 18.1 Lemoff and Rivkin (2008), p. 7-39.
  19. ↑ Lemoff and Rivkin (2008), p. 7-38.
  20. ↑ 20.0 20.1 Cholin (2008a), p. 14-106.
  21. ↑ Cholin (2008a), p. 14-100.
  22. ↑ 22.0 22.1 22.2 Mawhinney (2008), p. 16-140.
  23. ↑ 23.0 23.1 Madrzykowski and Stroup (2008), p. 2-43.
  24. ↑ Lataille (2008), p. 8-6.
  25. ↑ DeGiorgio and Peterkin (2008), pp. 9-127–9-128.
  26. ↑ 26.0 26.1 DeGiorgio and Peterkin (2008), pp. 9-124–9-125.
  27. ↑ Hirschler (2008a), p. 6-48.
  28. ↑ Tewarson (2002), p. 3-92.
  29. ↑ 29.0 29.1 Tewarson (2002), p. 3-93.
  30. ↑ Tewarson (2002), pp. 3-94–3-96.
  31. ↑ 31.0 31.1 31.2 Budnick et al. (2008), p. 3-160.
  32. ↑ DeGiorgio and Peterkin (2008), pp. 9-123–9-124.
  33. ↑ 33.0 33.1 Budnick et al. (2008), p. 3-161.
  34. ↑ 34.0 34.1 Dungan (2008a), p. 14-22.
  35. ↑ Hurley and Bukowski (2008), p. 3-129.
  36. ↑ Hirschler (2008a), p. 6-47.

References

  • Budnick, E. K., Hunt, S. P., & Wright, M. T. (2008). Closed form enclosure fire calculations. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-145–3-166). National Fire Protection Association.
  • Cholin, J. M. (2008a). Gas and vapor detection systems and monitors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-99–14-112). National Fire Protection Association.
  • DeGiorgio, V., & Peterkin, H. (2008). Semiconductor manufacturing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 9-119–9-129). National Fire Protection Association.
  • Dungan, K. W. (2008a). Automatic fire detectors. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 14-15–14-28). National Fire Protection Association.
  • Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-35–6-60). National Fire Protection Association.
  • Hurley, M. J., & Bukowski, R. W. (2008). Fire hazard analysis techniques. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 3-121–3-134). National Fire Protection Association.
  • Iqbal, N., & Salley, M. H. (2004). Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.
  • Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 8-3–8-15). National Fire Protection Association.
  • Lemoff, T. C. (2008). Gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 6-165–6-186). National Fire Protection Association.
  • Lemoff, T. C., & Rivkin, C. H. (2008). Storage of gases. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 7-35–7-42). National Fire Protection Association.
  • Madrzykowski, D., & Stroup, D. W. (2008). Flammability hazard of materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 2-31–2-48). National Fire Protection Association.
  • Mawhinney, J. R. (2008). Water mist fire suppression systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 16-135–16-180). National Fire Protection Association.
  • National Research Council of Canada, International Code Council, Department of Building and Housing, & Australian Building Codes Board. (2005). International fire engineering guidelines (2005 ed.). Australian Building Codes Board.
  • Tewarson, A. (2002). Generation of heat and chemical compounds in fires. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., & J. M. Watts Jr. (Eds.), SFPE handbook of fire protection engineering (3rd ed., pp. 3-82–3-161). National Fire Protection Association; Society of Fire Protection Engineers.
  • Webb, W. A. (2008). Air-Conditioning and ventilating systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., & R. E. Solomon (Eds.), Fire protection handbook (20th ed., pp. 10-69–10-76). National Fire Protection Association.