Contents
Fse-common-cause-failure-v4.svg (SVG file, nominally 900 × 600 pixels, file size: 8 KB)
Summary
One fire water supply serving several suppression systems: a single cause acting on the shared part disables all of them. Based on Barry (2002), p. 5-203 and Nowlen et al. (2005b), p. 13-7.
Original illustration for Common cause failure, level 4 Expert.
- Source basis: Barry (2002), p. 5-203 (fire pumps a common cause failure to numerous deluge water spray systems after pump house flooding; valves shut for fear of freezing); Nowlen et al. (2005b), p. 13-7 (fire pumps, firefighting water piping, standpipes and storage tanks as seismic common-cause items); redraw, do not copy
- Alt text: Schematic: one water tank and pump house feed a main that supplies three deluge systems; flood, freezing and earthquake act on the shared part.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:38, 2 November 2026 | 900 × 600 (8 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: