Fse-common-cause-failure-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)

Summary

Probability of losing sprinkler protection for one and two systems, with independent failures and with a shared water supply. Based on Parkinson et al. (1994), as cited in Nowlen et al. (2005b), p. P-6, and Barry (2002), p. 5-201.

Original illustration for Common cause failure, level 4 Expert.

  • Source basis: Parkinson et al. (1994), as cited in Nowlen et al. (2005b), p. P-6 (unreliability 0.02, excludes dependent failures and maintenance unavailability); Barry (2002), p. 5-201 (80 h per year downtime example)
  • Alt text: Log-scale bar chart: one system 0.02 or 0.029 with shared supply; two systems 0.0004 if independent, 0.0095 with shared supply.