Summary

Calculated temperature of a standard response sprinkler link in a 1,000 kW fire, without droplets and with liquid volume fractions of 1 and 2 millionths in the ceiling jet. Based on Iqbal and Salley (2004), pp. 10-15 to 10-18, and McGrattan et al. (2026), p. 107.

Original illustration for Sprinkler skipping, level 4 Expert.

  • Source basis: Iqbal and Salley (2004), pp. 10-15 to 10-18 (Example 10.10-1 and its spreadsheet values); McGrattan et al. (2026), p. 107 (link equation with droplet cooling term)
  • Alt text: Line chart: link temperature rising towards 88 °C; it reaches 74 °C at 174 s without droplets, 234 s and 361 s with droplets.