Contents
Fse-hydraulic-calculation-v2.svg (SVG file, nominally 900 × 600 pixels, file size: 9 KB)
Summary
Sample area and density curve converted to SI units. Any point on or to the right of the line is acceptable; the marked point is the selection of 6.1 mm/min over 223 m². Based on Fleming (2002), p. 4-74.
Original illustration for Hydraulic calculation, level 4 Expert.
- Source basis: Fleming (2002), p. 4-74 (Example 1 and the sample area/density curve in Figure 4-3.1: redraw, do not copy)
- Alt text: Chart of design area against water density: a falling straight line from 465 m2 at 4.1 mm/min to 139 m2 at 6.9 mm/min, region to its right shaded.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:28, 2 November 2026 | 900 × 600 (9 KB) | Jan (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.