Pressure difference between a pressurised 20-storey stair and the building, with −10 °C outside and 21 °C in the stair. Based on Klote (2002), p. 4-288.
Original vector illustration for Stair pressurisation, level 2 Intermediate.
- Source basis: Klote (2002), p. 4-288 (Equation 14, Example 4)
- Alt text: Line chart: pressure difference between stair and building rising in a straight line from 20 Pa at the bottom to 106 Pa at the top of a 66 m stair.