Summary

Calculated smoke leakage through a 30 m² wall at 200 °C and 25 Pa for different tightness levels, compared with the permitted leakage of one single-leaf smoke door. Based on Australian Building Codes Board (2020a), Data Sheet C5, pp. 149 to 155.

Original vector illustration for Smoke barrier, level 2 Intermediate.

  • Source basis: Australian Building Codes Board (2020a), Data Sheet C5, pp. 149 to 155; Van Rossum (2027), §5.3
  • Alt text: Bar chart of leakage in cubic metres per hour for a 30 square metre wall: tight 9, average 58, with services 86, loose 201, plus 40 for one smoke door.