Application rates for overhead hangar deluge protection with water, protein foam and AFFF. Based on Scheffey (2002), pp. 4-107, 4-108 and 4-112.

Original vector illustration for Deluge system, level 2 Intermediate.

  • Source basis: Scheffey (2002), p. 4-107 (water deluge and protein foam rates), p. 4-108 (NFPA 409 reduction to 6.6), p. 4-112 (NFPA 16 minimum 6.6 and AFFF effectiveness at 4.1)
  • Alt text: Bar chart of application rates: water deluge 10.4, protein foam 8.2, AFFF through standard sprinklers 6.6, AFFF effective on pool fires 4.1 L/min per m2.