Summary
Infrared flame detectors in an aircraft hangar: the detection distance for a 1.0 m² fire falls from 40 m on axis to about 25.6 m at the edge of the view, still above the 20 m needed. Based on Schifiliti et al. (2002), pp. 4-31 to 4-32.
Original vector illustration for Flame detector, level 2 Intermediate.
- Source basis: Schifiliti et al. (2002), p. 4-31 (Example 21; Figure 4-1.11 detector layout, redraw, do not copy) and p. 4-32 (reductions)
- Alt text: Hangar cross-section with flame detectors in the upper corners, their 45 degree fields of view and a 1 square metre pool fire on the floor.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.