Summary

Pulsation frequency of fire flames against burner or pool diameter, from the curve fit of Cetegen and Ahmed. Based on Heskestad (2002), pp. 2-14–2-15.

Original illustration for Turbulence, level 4 Expert.

  • Source basis: Heskestad (2002), pp. 2-14–2-15
  • Alt text: Log-log line falling from about 9 Hz at 3 cm to 0.3 Hz at 20 m, with points marked at 1 m and 2.6 m.