Contents
Fse-post-flashover-fire-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 14 KB)
Summary
Characteristic temperature curves (Lie) for the example office with heavy and light linings, compared with the ISO 834 standard fire curve. Based on Lie (2002), pp. 4-203 to 4-206.
Original vector illustration for Post-flashover fire, level 2 Intermediate.
- Source basis: Lie (2002), pp. 4-203 to 4-206 (Equations 1 to 8 and Table 4-8.2); fire load from Ministry of Business, Innovation and Employment (2025b), p. 22 (800 MJ/m², offices) converted at 18.8 MJ/kg (Walton and Thomas 2002, p. 3-184)
- Alt text: Line chart: two calculated fire curves peak at about 0.7 h and fall to ambient by about 1.7 h; the standard curve keeps rising to 1,010 °C at 2 h.
Licensing
New drawing by Fire Safety Academy. © Fire Safety Academy.
File history
Click on a date/time to view the file as it appeared at that time.
| Date/Time | Thumbnail | Dimensions | User | Comment | |
|---|---|---|---|---|---|
| current | 17:06, 2 November 2026 | 900 × 600 (14 KB) | Lisa (talk | contribs) | Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity |
You cannot overwrite this file.
File usage
The following page uses this file: