Skip to content
From Fire Safety Academy Wiki
Revision as of 17:05, 2 November 2026 by Lisa (talk | contribs) (Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Contents
  1. 1Summary
  2. 2Licensing

Fse-heat-release-rate-per-unit-area-v3.svg (SVG file, nominally 900 × 600 pixels, file size: 6 KB)

Summary

A t-squared fire at a constant 2,270 kW/m²: the diameter grows in proportion to time and the heat release rate with its square. Based on Heskestad (2002), p. 2-13 and Iqbal and Salley (2004), p. B-4.

Original vector illustration for Heat release rate per unit area, level 2 Intermediate.

  • Source basis: Heskestad (2002), p. 2-13 (growth time 140 s, 2,270 kW/m², D = 5.35 × 10⁻³ t); Iqbal and Salley (2004), p. B-4 (constant heat release rate per unit area and circular spread); Ministry of Business, Innovation and Employment (2013), p. 55
  • Alt text: Plan view of three concentric circles of burning fuel at 140, 280 and 420 s, with diameters 0.75, 1.5 and 2.25 m and fires of 1, 4 and 9 MW.

Licensing

New drawing by Fire Safety Academy. © Fire Safety Academy.

File history

Click on a date/time to view the file as it appeared at that time.

Date/TimeThumbnailDimensionsUserComment
current17:05, 2 November 2026Thumbnail for version as of 17:05, 2 November 2026900 × 600 (6 KB)Lisa (talk | contribs)Watermark: Fire Safety Academy logo icon, 70 px, 45 % opacity

The following page uses this file:

Metadata